アクセサリー dol sensors DOL 51のPDF テクニカル・ユーザー・マニュアルをオンラインで閲覧またはダウンロードできます。dol sensors DOL 51 8 ページ。 Ammonia sensor
5 Functions
NH3
5.6
7.2
8.8
10.4
Figure 4: Functional graph.
6 LED indication
LED indication
YELLOW flashing
slowly
Alternating GREEN
and YELLOW
Constant GREEN
GREEN flashing
quickly
Constant YELLOW
YELLOW flashing
quickly
DOL 51
13.6
15.2
16.8
18.4
Sensor status
Incorrect electrical supply or inter-
rupted supply.
Short circuit in supply cable.
Overvoltage or undervoltage at the
DOL 51 housing.
Incorrect voltage (e.g. 230 V AC)
applied, electronics damaged.
DOL 51 housing is defective.
Sensor is warming up to be ready
for measurements, signal level 0V
and 4mA.
Normal operation.
The ammonia concentration is be-
tween 40-60 ppm, which is used to
test the sensor. The sensor is
working, but it works as if it is in
test mode.
Internal fault detected by electron-
ics, signal level 0 V.
There is very little ammonia in the
livestock house – under 5 ppm, the
sensor output is 0V.
Action
Check installation for cable break. Check the
power supply unit of the control unit. Check elec-
tric voltage in the junction box or at the sensor el-
ement with a multimeter.
Check installation for short circuit.
Check electric voltage at the DOL 51 housing
with a multimeter.
Replace the DOL 51 housing.
Replace the DOL 51 housing, contact the sup-
plier.
No activity. Flashing stops after max. 30 minutes.
No activity. Flashing stops after max. 5 minutes.
Replace the DOL 51 housing.
Replace the sensor element, if the fault continues
for more than one day.
www.dol-sensors.com
Technical User Guide