- ページ 2

トランスデューサー Ashcroft A2XのPDF インストラクションシートをオンラインで閲覧またはダウンロードできます。Ashcroft A2X 2 ページ。 Exprosion/flame proof pressure transducer

A2X EXPLOSION/FLAME PROOF
PRESSURE TRANSDUCER
INSTRUCTION SHEET
Mounting
The A2X transmitter requires no special
mounting hardware, and can be mounted in
any plane with negligible position error.
Although the unit can withstand normal
vibration without damage or significant
C
output effects, it is always good practice to
mount the transducer where there is mini-
mum vibration.
1.062
For units with NPT type pressure fittings
PROCESS
FITTING
apply Teflon
tape or an equivalent sealant
®
(REF.)
to the threads before installing.
When tightening, apply a wrench to the
hex wrench flats located just above the
D
pressure fitting. DO NOT tighten by using a
pipe wrench on the housing.
Power Supply
.600
Power Supply Voltage
Output Signal
Min
0-5Vdc
10V
1-5Vdc
10V
(4) PIN BENDIX STYLE
ELECTRICAL TERMINATION
1-6Vdc
10V
SHELL SIZE 8
0-10V
14V
(B4), (H1), (L1), (P2)
4-20mA*
12V
* For transmitters with 4-20mA output
signal, the minimum voltage at the tem-
inals is 12Vdc. However, the minimum
supply voltage should be calculated using
the following graph and formula.
** For Intrinsically Safe Installations max,
supply voltage is 30Vdc. Refer to Ashcroft
drawing #825A022 for wiring and installa-
tion requirements.
Loop Supply Voltage vs. Loop Resistance
1000
30 Vdc max for
Intrinsically Safe
800
Installations
600
400
Operating
Region
200
0
20
10
Loop Supply Voltage (Vdc)
Vmin = 12V+ (.022A x RL) (includes a 10% safety factor)
RL = RS + RW
RL = Loop Resistance (ohms)
RS = Sense Resistance (ohms)
RW = Wire Resistance (ohms)
©2018 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. A2X_transducer_im_ RevB_(009-10167)_09-18
Noise
For minimum noise susceptibility, avoid
running the transducer's leads in a con-
duit that contains high current AC power
cables. Where possible avoid running the
cable near inductive equipment.
B
Sintered Metal Filter
All units less than 500 psi include a small
metal sintered filter at the top of the unit.
This is necessary to equalize the internal
pressure with atmospheric pressure but
1.062
1.000
can be a point of moisture ingress.
A2X Wiring Diagrams
A
POWER
SUPPLY
+
PIN 1
.830
PIN 2
Max
+
30V
METER
30V
OR OTHER DEVICE
PIGTAIL
ELECTRICAL TERMINATION
30V
CONDUIT - 1/2 NPT MALE
+
30V
POWER
(C1), (P7)
SUPPLY
30V**
ELECTRICAL TERMINATIONS FOR
WELDED HOUSINGS ONLY
+
EXCLUDING EXPLOSION PROOF
METER
OR OTHER DEVICE
A2X transducer has internal transient
protection: for safety, limit line-to-
ground voltage to 36 Vdc max.
HAZARDOUS AREA CERTIFICATIONS
Explosion Proof* – cUL: Specify A2X
Class I, Div. 1 & 2, Groups A, B, C and D
Class II, Div. 1 & 2, Groups E, F and G
Flame Proof* – ATEX: Specify A2X
Compliance with standards
EN 60079-0: 2012
and
EN 60079-1: 2007
II 2 G
Ex d IIC T4 Gb
-40°C ≤ Tamb. ≤ 125°C
DEMKO 04 ATEX 0237942
Intrinsically Safe (applies to 4-20mA) FM/CSA:
Intrinsic Safety: Class I, II and III Div.1 and 2,
30
36
Non-Incendive: Class I, II and III Div.1 and 2, Groups A,
*
Model A2X enclosure is intended for
installation using metallic conduit and
requires installer to comply with appro-
priate codes to complete proper instal-
lation to meet the assigned hazardous
area designation.
(+)
V+
TRANSDUCER
(–)
V–
4-20mA
PIN 1
(+ Power)
PIN 2
(Common)
TRANSDUCER
(+ Output)
PIN 3
3-Wire Voltage
C
B
1.062
PROCESS
FITTING
1.000
(REF.)
D
A
.600
(4) PIN BENDIX STYLE
Groups A, B, C, D, F and G per
ELECTRICAL TERMINATION
entity requirements see Ashcroft
SHELL SIZE 8
drawing # 825A022
(B4), (H1), (L1), (P2)
B, C, D, F and G, no
ELECTRICAL TERMINATIONS FOR
barriers needed
WELDED HOUSINGS ONLY
EXCLUDING EXPLOSION PROOF
Wire
Voltage
Color
Output
Red
(+) Power
(+) Power
White
(+) Output
Black
(-) Power
(-) Power
1.062
.830
FLYING LEADS
ELECTRICAL TERMINATION
CONDUIT - 1/2 NPT MALE
(C2), (C5)
ELECTRICAL TERMINATION FOR
*
Installation of conduit leads should be limit-
ed to 3m to maintain CE compliance
WELDED HOUSINGS ONLY
INCLUDING EXPLOSION PROOF
Wire
Voltage
Current
Color
Output
Output
Red
(+) Power
(+) Power
White
(+) Output
None
Black
(-) Power
(-) Power
1.062
.830
SHIELDED CABLE (PIG TAIL)
PIGTAIL
ELECTRICAL TERMINATION
ELECTRICAL TERMINATION
CONDUIT - 1/2NPT MALE
CONDUIT - 1/2 NPT MALE
(C1), (C6), (C7), (P7)
(C1), (P7)
Current
Output
None