Installation and Maintenance Instruction Manual for All
Stainless Steel Gas Actuated Thermometer Model S5500
(non-electrical device) in a configuration for explosion risk areas pursuant to
Directive 2014/34/EU (ATEX)Zone I and II, Category 2, Group II for gas and dust
• Hold the thermometer housing firmly with one hand, and
with the other hand turn the joint piece until the inner
part of the joint is showing in the desired direction of
bend.
• Firmly tighten the aforementioned Screws "A" again.
• Loose the screws marked "B" and move the joint into the
desired direction of bend.
• Firmly tighten the aforementioned Screws "B" again.
8.3.2 Process connection
• Connection only to be undertaken by authorized and
qualified specialist staff.
• Use only with the mechanical process connection
provided – regarding the configuration, see order code
on the device type label.
• When connecting the device without using a
thermowell, the pipes must be depressurized.
• Do not allow any mechanical force to be applied to the
stem; in particular, pay attention to matching the "S"
lengths of the thermometer and the thermowell, to avoid
contact against the base of the thermowell.
• A thermal transfer medium (heat conducting paste) in
the thermowell improves the reaction time and reduces
the measurement error caused by the thermal transfer.
• The minimum capillary line radius is 40 mm (1½˝). Place
it so that it will be protected from damage. Should the
capillary line be too long, coil the surplus neatly at a
convenient point but "DO NOT CUT IT."
• The thermometer system (Bourdon tube, capillary line
and temperature sensing bulb) must not, under any
circumstances be taken apart, or the capillary line cut.
Safety notice:
Only mount using the correct open-jawed
wrench, and do not twist the device itself.
Do not insert moist or oily stems into hot
thermowells
8.4 Starting up
• The precondition for start-up is correct installation. All
connecting lines must be laid such that no mechanical
forces can act on the device.
• Before start-up, the seal on the thermowell in the pipe
must be checked
© 2021 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. S5500_Gas_Act_Therm_RevA_(008-10293)_05-26-21
8.4.1 Zero point adjustment
• On thermometers with
an external adjustment
option, remove the plug
at the top of the case and
rotate using a screwdriver
until the pointer is
showing the desired
temperature on the scale
9 SERVICING
9.1 Safety
When undertaking servicing work on the device fitted
without a thermowell, the lines must be depressurized
and the plant secured against being switched on again.
9.2 Check on function and calibration
The check on function and recalibration is carried out
at regular intervals, depending on the application. The
precise testing cycles should be adjusted in line with the
operating conditions and ambient conditions
• Check on display.
• Check the thermowell for damage and seal.
9.3 Cleaning and maintenance
10 FAULT
10.1 Safety
Defective or faulty gauges put the operational safety and
process safety of the plant at risk, and can lead to a risk
or injury to persons, the environment or the plant.
10.2 Conduct in the event of faults
All defective or faulty devices are to be taken out of service.
If a repair is required, the device is to be sent directly to our
Repairs Department. We request that all returns of devices
are agreed with our Service Department.
10.3 Fault table
• Jerky or random movement of the pointer
• No correspondence between the measured value being
displayed and actual temperature
• Damage to housing
• Bended stem or bulb
• Bent or loose pointer
• Cracked window