Use SHIFT key to shift cursor to desire digit and INC key to change the desire digit from 0 to 9. The High
Alarm can be set throughout the range.
Press MODE key to proceed further. After pressing MODE key, the microcontroller will save High Alarm
setting for stream no. 01 and move to next parameter.
In the same sequential process, the following parameters for each Stream can be set :
Low Alarm for Streams 2 to 6.
High Alarm for Streams 2 to 6.
Press MODE key to proceed further. After pressing MODE key, the microcontroller will save High Alarm
setting for stream no. 06 and exit from STREAM ALARMS MODE.
This completesthe Stream Alarm settings.
After pressing MODE key, the OLED Display will return to the normal PROCESS SCREEN.
RETRANSMISSION (4-20mA DC) OUTPUT CALIBRATION MODE
The ASHE Stream Selector Model STL-96provides individual 4 to 20mA retransmission output for each
stream. All retransmission outputs are factory calibrated and donotrequire recalibration at the
customer's side. So do not enter into Retransmission Calibration Mode unless the instrument requires
recalibration.
Before entering into Input Calibration Mode, ensure that a reliable 4 to 20mA source is connected to
the instrument at the Input terminals with correct polarity.
Feed a DC current less than 4mA the source to the instrument. The process value on the OLED Display
will show "Low".
Enter the number 05 into Select Menu by using INC key in the PARAMETER SETTING MODE SCREEN.
Press the MODE key to enter into Retransmission Output Calibration Mode.
The OLED Display shows:
Press SHIFT key to move the cursor to the last digit.
Enter the Password 0004 by using INC key and press MODE key.
After pressing MODE key the OLED Display will show:
Password
0000
O/P zero adjust 01
34
ASHE CONTROLS PRIVATE LIMITED.
S
S
STL-96
TREAM
ELECTOR
Operation Manual