- ページ 14

計測機器 DOLD VARIMETER IMD RN 5897/011のPDF マニュアルをオンラインで閲覧またはダウンロードできます。DOLD VARIMETER IMD RN 5897/011 17 ページ。 Insulation monitor

Parameter table
Coils
Register-
Protocol-
Name
Adress
Adress
1
0
Reset
2
1
Device reset
3
2
Reserved
4
3
Factory setting
5
4
Device selftesting
6
5
Fault memory
indicator relay K1 + K2
7
6
Reserved
8
7
Advanced Test
Value
Initial
Description
range
value
0x0000
0x0000
No Function
0xFF00
Error acknowledgement device error
0x0000
0x0000
No Function
0xFF00
Device restart
0x0000
0x0000
-
0xFF00
0x0000
0x0000
No Function
0xFF00
Factory setting of the parameters
0x0000
0x0000
No Function
0xFF00
Selftesting
0x0000
0x0000
No Function
0xFF00
Fault memory acknowledgement
indicator relay K1 and K2
0x0000
0x0000
-
0xFF00
0x0000
0x0000
No Function
0xFF00
Advanced Test
14
Data type
Access rights
BIT
write / read
BIT
write / read
BIT
-
BIT
write / read
BIT
write / read
BIT
write / read
BIT
-
BIT
write / read
30.06.23 de / 752A