Step 2: Install and configure Repeaters and GBC/HUB at locations
defined by wireless survey
3.3
Step 3: Install, configure and initial calibrate the WPTs.
3.4
Step 4: Setup the GBC by entering the WPT and Repeater information
3.5
Step 5: If not connecting to a BAS, setup node groups and schedules
3.6
Step 6: If connecting to a BAS, discover WPT objects in your BAS
system through BACnet/IP
3.6.1
Reference document: 910-00008-01, WPT BACnet PICS
4 System Usage
4.1
Resources
The section below will provide basic information. Please refer to the specific product
manuals or the GBC web application manual for details. These documents are listed
under Section 1.2.
4.2
At the thermostat
4.2.1
View the current zone temperature
1. The current zone temperature is shown on the WPT display. While the WPT
continually monitors and adjusts for changes in temperature, the display will only
be updated every 5-15 minutes (depending on the sample rate of the WPT).
4.2.2
View or change the current setpoint (single setpoint)
1. Press the up or down button at the thermostat. You will then see a number start to
flash with the thermometer icon on the left. The thermometer icon indicates this is
the setpoint. The flashing number is the current setpoint.
2. Once the number is flashing, press up or down to raise or lower the setpoint.
Press the center button to save and exit the setpoint menu.
4.2.3
View or change the current setpoint (deadband thermostat)
1. Press the up or down button at the thermostat. You will then see two numbers
alternating on the display with thermometer icon on the left. The thermometer icon
indicates these are the setpoints. The higher number is the cool above setpoint
and the lower number is the heat below setpoint. When the zone temperature is in
between these two numbers, the thermostat will adjust to a neutral pressure. When
the zone temperature is higher than the cool above setpoint, the thermostat will
switch to cooling. Likewise, if the zone temperature is lower than the heat below
setpoint, the thermostat will call for heating.
2. Once the numbers are flashing, press up or down to raise or lower the setpoints.
The deadband span will remain the same. For example, if the current deadband
setpoints are 74 and 70 and you press up once to raise the setpoints, the new
setpoints will be 75 and 71 with the same 4 degree deadband. Press the center
button to save and exit the setpoint menu.
WPT Operations and Maintenance
Document No. 910-00028-01, Rev 1
Page 3 of 10