Troubleshooting Tips for the 6033 Mini Universal Controller
(1) Open fuse detection (monitored continuously).
(2) Motor disconnected, or open motor circuit detection (checked once every time motor is turned on). When either
of these conditions are found, the Mini Universal will:
• Stop trying to run the motor
• Turn off input command indicators LED 1 or LED 6
• Turn OFF Relay K1 (Green LED = Retracted)
• Turn OFF Relay K2 (Red LED = Extended)
• Turn on FAULT indicator LED 3
• Remain in this condition until fault is cleared / fixed, AND power is turned off, then back on
(3) LED 1 and LED 6 are input signal command indicators. They should come on when the 6033 Mini Universal
Controller is being told to Extend, or to Retract.
(4) The "POWER OUT" LED at the top right side of the 6033 comes on Green when power is being sent out to the
Electric Riser motor to RETRACT the 3406 Riser.
(5) The "POWER OUT" LED at the top right side of the 6033 comes on Red when power is being sent out to the
Electric Riser motor to EXTEND the 3406 Riser.

MAINTENANCE INSTRUCTIONS

The electric riser should be inspected prior to and after each use to ensure it is in good operating condition. Periodically,
an unanticipated incident occurs where the unit is used in a manner that is inconsistent with standard operating prac-
tices. A partial list of these uses includes:
• Operating above the maximum rated pressure or flow.
• Prolonged exposure to temperatures above 130°F, or below -25°F.
• Operating in a corrosive environment.
• Having the monitor nozzle hit a fixed object during operation or transportation.
• Any misuse that might be unique to your specific environment.
Also, there are many "tell tale" signs that indicate repair is in order, such as:
• Controls that are either inoperable or difficult to operate.
• Excessive wear
• Poor discharge performance
• Water leaks.
If any of the above situations are encountered, the Riser/Monitor monitor should be taken out of service, repaired, and
tested by a qualified technician before placing back in service. Grease fittings are provided above the extension stops.
To lubricate the riser, place it in the extended position and wipe off any old grease residue from the tubes. Using a
manual grease gun, apply two shots of grease to each fitting.