waveform. This is where the supplementary ballast is used. If the power dissipated in
the main ballast is over a certain limit then the additional ballast is automatically
switched on and when its power drops below a certain limit it automatically switches
off.
The ELC is wired in parallel with the generator output so that it can't be inadvertantly
switched out of the circuit. The system is connected as follows:
hydro
turbine
Electronic Load
Controller - ELC
To connect the electrical components, please follow these steps:
The electrics should be installed by persons competent in mains voltage
wiring. This system operates on a switched neutral basis. Neutral and phase
connections to the load elements should be treated as live at all times!
1. Install the control box in a convenient location that is protected from rain and sun.
This may be either in a powerhouse along with the turbine or else in a house at the
user's end.
2. Earth-bond (ground) PowerPal. Do this by attaching one end of a suitable length
2
of 16mm
wire to PowerPal and the other end to a metal object or metal stake in
the ground nearby PowerPal.
3. Connect the generator to the control box. All wiring from the generator to the
control box, from the control box to the user load and from the control box to the
ballast load should be done using insulated multistrand copper wire, the size of
which is given in the Technical Specifications part of this manual.
The following wiring diagram shows the location of all connection points but note
that most components are already wired and installed within the control panel.
Main network or house
distribution board
Ballast load(s)
220VAC
house supply
PowerPal™ T8 & T16 Turgo 9