These units are designed for use in residential and
light commercial type buildings. Heat Pumps may only
be installed with indoor combinations listed in the Air
Conditioning, Heating and Refrigeration Institute (AHRI)
Directory of Certified Products.
Inspect the unit for any damage before installation. If
damage is found, notify the transportation company
immediately and file a concealed damage claim.

Safety Precautions

Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warning or cautions attached to
the unit.
1.
Always wear proper personal protection equipment.
2.
Always disconnect electrical power before removing
panel or servicing equipment.
3.
Keep hands and clothing away from moving parts.
4.
Handle refrigerant with caution, refer to proper MSDS
from refrigerant supplier.
5.
Use care when lifting, avoid contact with sharp edges.

Installation

NOTE: In some cases noise in the living area has been
traced to gas pulsations from improper installation of
equipment.
1. Locate unit away form windows, patios, decks, etc.
where unit operation sounds may disturb customer.
2.
Ensure that vapor and liquid tube diameters are
appropriate to capacity of unit.
3.
Run refrigerant tubes as directly as possible by
avoiding unnecessary turns and bends.
4.
Leave some slack between structure and unit to
absorb vibration.
5.
When passing refrigerant tubes through the wall, seal
opening with RTV or other silicon-based caulk.
6.
Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, walls, and any structure.
7.
Do not suspend refrigerant tubing from joists and
studs with a rigid wire or strap which comes in direct
contact with tubing.
8.
Ensure that tubing insulation is pliable and completely
surrounds vapor tube.
When outdoor unit is connected to factory-approved indoor
unit, outdoor unit contains system refrigerant charge for
operation with indoor unit of the same size when connected
by 15 ft. of field-supplied tubing. For proper unit operation,
check refrigerant charge using charging information
located on control box cover.
Page 2 of 11
NOTE: Maximum liquid-line size is 3/8 in. O.D. for all
residential applications including long lines.
Outdoor Section
Zoning ordinances may govern the minimum distance the
condensing unit can be installed from the property line.
Install on a Solid, Level Mounting Pad
The outdoor section is to be installed on a solid foundation.
This foundation should extend a minimum of 2" (inches)
beyond the sides of the outdoor section. To reduce the
possibility of noise transmission, the foundation slab
should NOT be in contact with or be an integral part of the
building foundation.
Elevate Unit
Accumulation of water and ice in base pan may cause
equipment damage.
Elevate unit per local climate and code requirements to
provide clearance above estimated snowfall level and
ensure adequate drainage of unit. Use snow stand in areas
where prolonged freezing temperatures are encountered.
If conditions or local codes require the unit be attached to
pad or mounting frame, tie down bolts should be used and
fastened through knockouts provided in unit base pan.
Rooftop Installations
Mount on level platform or frame 6 inches above roof
surface. Place unit above a load-bearing wall and isolate
unit and tubing set from structure. Arrange supporting
members to adequately support unit and minimize
transmission of vibration to building. Ensure roof structure
and anchoring method is adequate for location. Consult
local codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may
require wind baffles to achieve adequate defrost. A sheet
metal baffle should be spaced 6-1/2" from the fall of the
coil. The height should cover the face of the coil and the
length should be 6" from the access panel.
NOTE: Unit must be level to within ± 1/4 in./ft. per
compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. For proper airflow,
quiet operation and maximum efficiency. Position so water,
snow, or ice from roof or eaves cannot fall directly on unit.
Issue 1850
CAUTION
506318-03B