Ambirad TORNADO 설치 및 운영 매뉴얼 - 페이지 11
{카테고리_이름} Ambirad TORNADO에 대한 설치 및 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Ambirad TORNADO 16 페이지. Gas fired mobile heater
Ambirad TORNADO에 대해서도 마찬가지입니다: 사용 설명서 (8 페이지)
To replace the electronic sequence controller,
transformer, thermostat and pressure switch.
Access to these components is via the hinged lid.
Remove the lid securing screws.
Components can be seen behind the hinged lid.
Replace as required ensuring connections are
made in the same order as on removal.
To replace (or reset) the thermal cut out
switch.
Place the product on the rear ring in the vertical
position to gain access to the fan cover.
Remove the fan access cover.
The thermal cut out is located on the inside back
wall and can be changed by removing the two self
tapping screws.
To reset a failed thermal cut out, press the small
button located in the centre of the product.
Vacuum Pressure Switch connections
2
2
3
Negative pressure
1
Positive pressure
3
P
1