AMC AMC-1224 사용 설명서 - 페이지 8
{카테고리_이름} AMC AMC-1224에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. AMC AMC-1224 17 페이지. Sensor modules
4 INSTALLATION
This section discusses topics relating to the proper installation of the AMC-1225 unit. The
proper location, sensor wiring selection and multi-unit interconnection are all discussed in detail
in the following section.
4.1 LOCATION AND MOUNTING
Mount the sensor unit on a solid non-vibrating surface or structure easily accessible for status
checking and calibration. The unit must be mounted in an area where the local concentration of
gas is unaffected by the presence of ventilation systems.
4.1.1 MOUNTING
1. Remove cover and mounting bracket with transmitter.
2. Mount housing using defined mounting holes.
3. Drill holes for conduit and then install conduit. See Warning below.
4. Reattach cover and bracket.
Warning:
Conduit should enter the housing from the bottom to ensure best protection against
ingress of condensation.
Conduit entry from the top from the top of the housing is Not Recommended.
However, if conduit entry through the top is the only available option, a Condensation
Drip Shield is provided to help protect the electronics from water ingress due to
condensation from the EMT conduit. If conduit entry is through the top of the housing,
a drain hole must be drilled into the bottom side of the housing to allow the
condensation to exit the housing. Any water damage related to conduit entry from the
top will not be covered under warranty.
NOTE:
Mounting arrangement of the housing depends on location and mounting surface.
Mounting hardware is NOT supplied.
AMC-1225 SENSOR MODULES
7