QUICK START
Coolant Management System
INSTRUCTIONS
FILL TANK – METHOD 1 POUR IN
Ensure there is no pressure or vacuum in the new coolant
tank by pulling up on the relief valve ring on top of the tank.
Remove the fill cap. Add the required amount of new
coolant and replace the fill cap.
FILL TANK - METHOD 2 VACUUM MODE
If the Fluid Tank gauge indicates pressure or a vacuum,
turn Tank Control to VENT to equalize tank to zero.
Close the ball valve on the BLACK service hose and
connect the open-end adapter.
Turn Tank Control and Vacuum Control to Yellow.
Move the Flow Control to "ON".
Place the open-end adapter into a new coolant container
and open the ball valve on BLACK hose.
When the coolant level in coolant tank reaches the desired
level, move the Flow Control to "OFF" and close the ball
valve on the BLACK service hose.
Move Vacuum Control to OFF and move Tank Control to
VENT.