American Rotary AMP 10 사용자 설명서 - 페이지 9
{카테고리_이름} American Rotary AMP 10에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. American Rotary AMP 10 18 페이지.
4.0 CIRCUIT BREAKER CONSIDERATIONS
FOR 208V - 240V
For all voltages: Breakers recommended are based off of the largest single load that is able to be started .
Always consult NEC and local codes for breaker sizing . The below chart does not replace or supersede any
requirements by local, state, or national electric codes .
MODEL
AMP 5
AMP 10
AMP 20
NOTE
All AMP units come standard with a 50AMP Single Phase Plug . This unit must plug into a
6-50R receptacle, if you do not have this please contact American Rotary to purchase one .
*If you run more than 10HP(28AMPS) the provided 50AMP Cord and plug should be removed
and the AMP unit should be hard wired into your single phase breaker .
9 | User Manual R2 .3
LARGEST LOAD FOR
OPTIMAL
KVA
PERFORMANCE
HP (AMPS)
2 .5
2 .5 (7)
5
5 (14)
10
10 (28)
MAX TOTAL LOAD
RUNNING
BREAKER SIZE
HP (AMPS)
5 (14)
10 (26)
20 (56)*
MIN 1-PHASE
(AMPS)
20
40
50