BOCK EzFit EZ 100-76N 사용 설명서 - 페이지 8
{카테고리_이름} BOCK EzFit EZ 100-76N에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. BOCK EzFit EZ 100-76N 11 페이지.
SECTION V: OPERATION (cont .)
INSPECT THE INSTALLATION AND ADJUST THE CONTROLS
During the initial warm-up of the stored water, check for proper combustion by sampling
combustion gas at a point just below the exit of the flue. O
of 4.5-5.0% with CO levels at 0 ppm. Both combustion chamber access panels and insulation
(placed between panels) shall be installed when performing the combustion test. O
that greatly deviate from the specified range may lead to unsafe operating conditions.
Factors that can lead to O
levels outside of the specified range include inadequate or excess
2
draft caused by ambient conditions or venting, obstructions underneath the water heater
preventing sufficient flow of air to burner, and improper inlet or manifold gas pressures. For
natural gas, the manifold pressure is preset at 4.0" w.c. and the acceptable inlet pressure is in
the range of 5-14" w.c. For propane gas, the manifold pressure is preset at 10.0" w.c. and the
acceptable inlet pressure is in the range of 11-14" w.c. See the "Pre-Installation" section of this
manual for information on clearances, air supply, and venting.
The thermostat has been adjusted to 120°F at the factory. Wait until thermostat has shut
off gas to the main burner. Wait 30 seconds following shut-off of gas, then set thermostat
to the highest temperature. The main burner should relight. Set thermostat to the lowest
temperature; the main burner should go out. The thermostat should be adjusted to the
minimum setting that will meet the hot water needs of the homeowner or commercial
application.
There is a scald potential if the thermostat is set too high. The recommended temperature
setting for normal residential use is 120°F. If higher temperature settings are needed for
combined appliance applications or commercial use, an automatic tempering valve
must be installed on all domestic hot water lines.
MEASURING THE OUTCOMING WATER TEMPERATURE
The thermostat is factory set at 120°F for
domestic use. It is the responsibility of the
building owner to verify that the installer
follows the recommended quantitative testing
for measuring the outlet water temperature. To
make sure that the system works properly after
installation and in the future, it is recommended
that the heater's performance be measured and
monitored. Run water out of the tap nearest
the heater until it comes out warm. Using a
calibrated thermometer, take a measurement. If
the water is not at a suitable temperature for the
installation, have a qualified service person adjust
the temperature control. Contact Bock for further
information if needed.
This log (or a similar one) should be filled out as
follows:
Date
Time
Person running test
Page 14
readings should be in the range
2
readings
2
CAUTION
Figure 6: Approximate Temperature and
Dial Setting Relationship
Set temp °F
Outlet temp °F
Atmospheric Gas
SECTION VI: MAINTENANCE
NOTICE TO THE OWNER: If you are having a mechanical problem with your water heater,
contact your service company or installer.
WATER PIPING
On an annual basis, all piping should be checked for leakage at joints, shut-off valves, and
unions.
T&P RELIEF VALVE
On an annual basis, the temperature and pressure relief valve should be checked for proper
operation. First, attach a drain line to the valve to direct the water discharge to an open drain.
This is very important because the temperature of the discharge could be very hot. Second,
lift the lever at the end of the valve several times. The valve should operate freely and return
to its original position properly. If water does not flow out of the valve, remove and inspect
for corrosion or obstructions. Replace with a new valve if necessary. Do not repair the faulty
valve as this may cause improper operation.
ANODE RODS
Anode rods should be inspected twice in the first year and at least yearly once a time interval
for inspection has been developed. It is recommended to check the rod(s) six months after the
heater is installed. If the anode rod had reduced in size by two-thirds of its original diameter
of 3/4" or shows signs of pitting, it is time for replacement. Take the following steps when
changing the anode rod(s):
1. Shut off water supply.
2. Open any faucet to relieve tank pressure.
3. Remove caps on water heater top; push insulation aside.
4. Use a 1 1/16" six-sided socket wrench and a breaker bar. Snap hard to break the anode
rod seal.
5. Remove rod(s) and replace with new rod(s).
6. Turn water supply back on and leave faucet open until air is out of line.
7. Turn faucet off and check that new rod(s) doesn't leak.
8. Snap caps back into place.
FLUSH THE TANK
Elements in the water such as lime and iron may accumulate in the heater. Accumulation of
these elements can keep your water heater from operating at peak efficiency and may lead to
premature tank failure. It is recommended that the tank is drained and flushed thoroughly
once a year to prevent buildup.
Atmospheric Gas
Page 15