8.3
Each room airflow rate will need to be recorded on the Inspection
Checklist and Airflow measurement Test Sheet. A completed copy must
accompany these instructions and be handed over to the dwelling's
owner upon completion of the installation.

9.0 System Balancing

• Fully open all of the air valves (see figure 11).
• Switch the system to boost.
• Close all internal and external doors and windows.
• measure the total air volume of the extract valves (wet rooms).
• To adjust the 'boost' control on the wiring centre in order to
achieve the whole dwelling extract ventilation rate, remove the rubber
tamper-deterrent cap and use Domus Ventilation commissioning
adjustment tool, SPR439.
V E N T I L A T I O N
CMX-MULTI
www.domusventilation.co.uk
-
purge boost trickle
• Adjust individual room air valves to achieve the individual room
boost extract rates.
• Switch the system to low.
• measure the total air volume of the valves.
• To adjust the 'trickle' control on the wiring centre in order to
achieve the whole dwelling extract ventilation rate, remove the rubber
tamper-deterrent cap and use Domus Ventilation commissioning
adjustment tool, SPR439.
V E N T I L A T I O N
CMX-MULTI
www.domusventilation.co.uk
+
-
%RH
purge boost trickle
• To adjust the 'remote humidity' (%RH) sensor on the wiring centre,
remove the rubber tamper-deterrent cap and use Domus Ventilation
commissioning adjustment tool, SPR439.
• Using the lock nuts fitted to the air valves, lock in position (see
figure 11).
• Refit the rubber tamper deterrent caps to the lid of the wiring
centre.
Technical or commercial considerations may, from time to time, make it
necessary to alter the design, performance and dimensions of equipment
and the right is reserved to make such changes without prior notice.
Domus Ventilation
Block C, Van Court, Caerphilly CF83 3ED, United Kingdom
Tel: 03443 715 523
www.domusventilation.co.uk
LAB1356R | NoVEmBER 2018
+
+
+
-
-
+
+
+
-
-
-
11

10.0 Maintenance

The CMX-MULTI / CMX-MULTI-H appliance is essentially maintenance
free.

11.0 Warranty

The 2 year warranty starts from the day of delivery and includes first
year parts and labour, remaining year parts only. This warranty is void if
the equipment is modified without authorisation, is incorrectly applied,
misused, disassembled, or not installed, commissioned and maintained
in accordance with the details contained in this manual and general
good practice.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Conditions of Sale. Customers purchasing from
outside of the UK should contact Domus Ventilation Sales office for
further details.
The above warranty does not apply to nor cover the repair of any
problem or fault with the product which arises as a result of: (a) failure
to install, operate, maintain and/or repair the product or any associated
parts and components (including any ducting) using reasonable skill
and care and in accordance with the instructions provided with it
(unless the original installation, maintenance or repair which gave rise
to the problem or fault was carried out by or on the behalf of Domus
Ventilation in which case this exclusion will not apply); (b) use of the
product for any purposes other than those for which it is designed;
(c) modifications made to the product by anyone other than Domus
Ventilation or its approved contractors; (d) deliberate damage; and/or (e)
damage caused by fire, flood or other water damage, explosions, rust or
corrosion.

12.0 TECHNICAL SUPPORT

For technical assistance or further product information, including spare
parts and replacement components, please contact Domus Ventilation
via below contact details.
Telephone 03443 715 523
PAGE 6