Ekinex EK-GC1-TP 빠른 시작 매뉴얼 - 페이지 3
{카테고리_이름} Ekinex EK-GC1-TP에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Ekinex EK-GC1-TP 4 페이지. Led dimmer-actuator 4 channels rgbw
12..30 VDC
12..30 VDC
C1/R
+
+
-
-
-
−
+
N
L
Area
Line
Dev.
bus KNX
+
Bus
KNX
-
Characteristics of the terminals
• cage clamping of conductors
• maximum cross section of conductor 2.5 mm² (single-
wire) or 1.5 mm² (multi-wire)
• recommended wire stripping approx. 6 mm
• torque max 0.5 Nm
Configuration and commissioning
Configuration and commissioning of the device require
the use of the ETS
(Engineering Tool Software) program
®
V4 or later releases. These activities must be carried out
according to the design of the building automation system
done by a qualified planner.
i
Note. The configuration and commissioning of KNX
devices require specialized skills. To acquire these
skills, you should attend the workshops at KNX cer-
tified training centers.
Configuration
For the configuration of the device parameters the corre-
sponding application program or the whole ekinex
duct database must be loaded in the ETS program. For
detailed information on configuration options, refer to the
application manual of the device available on the website
www.ekinex.com.
Application program
Code
(## = version)
EK-GC1-TP
APEKGC1TP##.knxprod
Commissioning
For commissioning the device the following activities are
required:
• make the electrical connections as described above;
• turn on the bus power supply;
• switch the device operation to the programming
modeby pressing the programming pushbutton loca-
(R)
LED strip
(G)
LED strip
(B)
LED strip
(W)
LED strip
C2/G
C3/B
C4/W
-
-
-
230V~/6A max
L
110-230 Vac
50/60 Hz
N
®
Communica-
Group ad-
tion
dresses
objects
(max. nr.)
(max. nr.)
160
160
ted on the front side of the housing. In this mode of
operation,the programming LED is turned on;
• download into the device the physical address and the
configuration with the ETS
At the end of the download the operation of the device
automatically returns to normal mode; in this mode the
programming LED is turned off. Now the bus device is
programmed and ready for use.
Dimensions [mm]
12..30 VDC
12..30 VDC
+
+
-
Area
Line
Dev.
bus KNX
Marks
• KNX
• CE: the device complies with the Low Voltage Directi-
ve (2014/35/UE) and the Electromagnetic Compatibility
Directive (2014/30/UE). For a detailed list of the valid
norms, please refer to the appropriate document decla-
ring their compatibility.
Maintenance
The device is maintenance-free. To clean use a dry cloth.
It must be avoided the use of solvents or other aggressive
substances.
Smaltimento
Warning! Incorrect disposal of this product may
!
cause serious damage to the environment and hu-
pro-
man health. Please be informed about the correct
disposal procedures for waste collecting and pro-
cessing provided by local authorities.
Document
This datasheet refers to the release A1.0 of the ekinex
device EK-GA1-TP, and is available for download at www.
ekinex.com as a PDF (Portable Data Format) file.
File name
STEKGC1TP_IT.pdf
3
program.
®
70
72
30
C1/R
C2/G
C3/B
C4/W
-
-
-
-
-
230V~/6A max
At the end of its useful life the product de-
scribed in this datasheet is classified as wa-
ste from electronic equipment and cannot
be disposed together with the municipal
undifferentiated solid waste.
Device release
A1.0
20
20
®
Updating
04 / 2017