Output VDC
Switch Position
12VDC
24VDC
Stand-by Specifications:
Output
12VDC / 7 AH Battery
24VDC / 7 AH Battery
Note: For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage.
When standby batteries are used, they must be lead-acid or gel type.
Red (DC)
Green (AC)
ON
ON
ON
OFF
OFF
ON
OFF
OFF
Battery Back-up: Use sealed lead-acid 12 volt secondary lead-acid only. Connect two in series for 24 volts.
When using standby batteries house them in a separate enclosure.
Terminal Legend
TRG1 & TRG2
LOCK+
STRIKE+
NC, NO, C (adjoining)
TRG1 & TRG2
AUX+
COM –, AUX –,
BAT –, GND
(adjoining RST)
GND (adjoining TR)
FACP
BAT +, BAT –
RES & GND
TRG &
GND
Equipment and systems intended to be operated with a sensor release feature shall be constructed to operate so that when the sensor
detects an occupant within 5 feet of the egress side of the door, the door locking mechanism will unlock the door.
PS17-TD2

Power Supply Output Specifications:

Max Load DC
SWI ON
SWI OFF
4 hr. of Stand-by & 5 Minutes of Alarm
Stand-by = 1.25A
Alarm = 1.25A
Power Supply Status
Normal output, powered by AC.
Battery backup is powering output.
No DC output.
Loss of AC. Discharged or missing stand-by battery. No DC output.

Terminal Identification:

Function/Description
These input terminals are designed to connect to the closed C and NO terminals of an access control or fire
alarm relay. These must be jumped otherwise. These terminals control LOCK +, and STRIKE +, as well as
PS17-TD2 output relay contacts NC, NO, C.
This terminal provides DC output voltage when TRG1 and TRG2 are shorted together and are typically used
to power electromagnetic locks. Two locks may be connected in parallel on LOCK + and COM –
(fig. 2, pg. 4).
This terminal provides DC output voltage when TRG1 and TRG2 are unshorted and are typically used to
power Electric Strikes.
Isolated dry Form "C" contacts. Shortening TRG1 and TRG2 together causes these contacts to switch. They
are typically used for controlling multiple power supplies with fire alarm tie-in (fig. 4 and 5, pg. 7).
Continuous positive (+) DC power output voltage. It is not affected by TRG1, TRG2 operation.
Are all common (–) output (ground)
Spare wiring terminal used for fire alarm tie-in application (fig. 3, pg. 5)
Battery back-up connections. Apply proper voltage SLA batteries.
Batteries are trickle charged with 13.6 or 26.6 volts.
Are normally open. To reset either time delay at any time-closed momentarily.
Trigger either Delayed Egress or Access-controlled Egress by closing momentarily TR to G.
If nuisance delay is on in Delayed Egress Mode, trigger must be closed continuously for one full second.
1.75A
1.75A

LED Diagnostics: