AmeriWater SCALA2 운영 및 유지보수 매뉴얼 - 페이지 10

{카테고리_이름} AmeriWater SCALA2에 대한 운영 및 유지보수 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. AmeriWater SCALA2 14 페이지. Booster pump

AmeriWater SCALA2 운영 및 유지보수 매뉴얼
PUMP CONTROLS
Function
Default
Self-learning
Auto reset
Anti cycling
Maximum
continuous
operating time

4.2.1 Resetting to Factory Settings

The pump can be reset to factory setting by pressing and holding the DOWN and RESET buttons
simultaneously for 5 seconds.
8
On
If the pump cannot reach the user-defined pressure setpoint, the self-
learning function will automatically adjust the setpoint. The pump will
lower the setpoint to either 65, 51, or 36 psi.
The self-learned setpoint is indicated on the operating panel by one
flashing green light.
After every 24 hours, the pump will automatically attempt to revert to
On
the original user-defined setpoint. If this is not possible, the pump will
again return to the self-learned setpoint. The pump will continue to
operate with the self-learning setpoint, until the user-defined setpoint
can be reached.
Off
If you set the self-learning function to off and the pump is unable to
reach the desired setpoint, the pump will show alarm 5.
On
This function allows the pump to automatically check if the operating
conditions are back to normal. If the operating conditions are back to
On
normal, the alarm indication will be reset automatically.
Off
All alarms must be reset manually by means of the RESET button.
This function monitors the starts and stops of the pump.
Off
If the pump starts 40 times in a fixed pattern, there will be an alarm.
Off
The pump will remain in operation as normal.
On
If the pump starts and stops in a fixed pattern, there is a leakage in the
system, and the pump will stop and show alarm 3.
This function is a timer that can turn off the pump if it runs continuously
for 30 minutes.
Off
If the pump exceeds the running time of 30 minutes, the pump will run
Off
depending on the flow.
On
If the pump exceeds the running time of 30 minutes, the pump will stop
after 30 minutes of continuous operation, and it will show alarm 6. This
alarm will always need to be reset manually.
SCALA2 BOOSTER PUMP
Description
98-2039 Rev A