Normal Status of the LED's on the Motor Driver Board(Overview)
1. On power up, the GREEN LED on the lower left of the Motor Driver board should
2. The Motor Driver board RED LED should be OFF on initial power up, but after
several seconds should briefly flash ON for less than a second, then go back off***
3. The Power Supply board Green LED's for 24V, 5V should be ON
4. The Main Board Green LED's for 5V, 3.3V should be ON.
***On power up, if the RED Fault LED on the motor driver board is lit right away, then
1. The Motor Logic cable is not plugged in from the Master Controller to the motor.
2. On the motor, there is a set of five wires that go to the small circuit board located
on the motor. This set of wires may be damaged, or the plug is not seated properly.
3. If the motor has been plugged into the Master Controller using ANY port other
than the MTR Logic port, the motor may have been damaged causing this fault.
Dado Master Controller Unit
LED Status Indicators
MAIN BOARD
POWER SUPPLY
BOARD
always be on.
there is a problem:
See additional information on troubleshooting.