S2000-IP-03 Analog Addressable Rate-of-Rise and Fixed Temperature Heat Detector (hereinafter referred to as the detector) of Response Class A1R is to be
used in fire alarm systems to protect premises against fires by monitoring the rate of ambient temperature rise, exceeding the response value, and sending Fire
Alarm, Fire Prealarm, or Norm messages. The detector operates under a polling loop controller S2000-KDL or S2000-KDL-2I as a part of an Orion Integrated
security system. Moreover, the S2000-IP-03 responds with the measured ambient temperature values in degrees Centigrade upon the relevant requests of the
network controller. The detector supports DPLS_v2.xx protocol and provides measuring of the addressable loop voltage at the point where it is connected.
Electromagnetic compatibility of the detector meets the requirements of the third immunity level in line with Russian standards. The version of S2000-IP-03
firmware is v.1.10. The detector can be tested by means of a laser-based tester (for example, manufactured by System Sensor).
1.2
Specifications
1) Fixed Temperature (factory setting)
2) Consumed Current
3) Input Loop Voltage
4) Pre-operation Time
5) Heat Detection Accuracy
6) Operation Temperature
7) Relative Humidity
8)
Ingress Protection Rating
9) Weight
10) Transportation and Storage Temperature
11) Overall Dimensions:
–
Diameter
–
Height
12) The detector does not contain precious materials (Clause 1.2 of Russian GOST 2.608-78).
2.1
Connection Diagram
Figure 1 shows a typical diagram for connecting the detector into the
polling loop of a polling loop controller. If the S2000-IP-03 is used as a fire
detector, the input type for the detector in the configuration of the polling loop
controller should be set to:
"3 – Heat Fire" for which the rate of rise of temperature and exceeding of
the +54 C maximum value are monitored, or
to the value "9 – Heat Analog Addressable" which provides defining
temperatures of thresholds for generating messages "Fire Prealarm" and
"Fire Alarm" (+54... +65 C) without regard to temperature rise rate.
If the detector is to be used for measuring ambient temperatures, the input type for the detector is to be set to the value "10 - Thermostatic".
For the S2000-KDL of versions v1.38 and below the input type for the detector should be "3 – Heat Fire".
To get information about input types and setting they in the controller configurations, please refer to the operating documentation for the polling loop
controller and Orion Pro Workstation.
The first terminal of the detector base can be used to connect a shield of the connecting wire.
2.2
Mounting
Detectors should be located in line with construction regulations of Russian СП 5.13130.2009.
The detector can be attached in accordance with one of the two variants below (Figure 2). To attach the detector to a solid surface (Variant A) the detector
base plate provided is used. Optionally, MK-2 Recessed Mounting Kit (Variant B) can be purchased additionally to install the detector into a suspended ceiling.
A
Figure 3 shows the drilling pattern to install the detector base plate for Variant A as well as the diameter of a mounting hole in a suspended ceiling for
Variant B.
A T T E N T I O N !
To install the detector into the base plate, align the guide on the detector with the short guide of the base plate. Then turn the detector clockwise
until the detector guide is aligned with the guide 3 as shown in Figure 2(A).
ANALOG ADDRESSABLE
RATE-OF-RISE AND FIXED TEMPERATURE DETECTOR
1
2
OPERATION INSTRUCTIONS
B
Figure 2
S2000-IP-03
INSTRUCTION MANUAL
TECHNICAL DATA
- +54°C
- max 0.5 mA
- 8 V to 11 V
- max 60 s
- ± 1.5°C
- Minus 30°C to +55°C
- Up to 93% at +40°C
- IP41
- max 0.2 kg
- Minus 50°C to +50°C
- max 100 mm
- max 47 mm
S2000-KDL
+PL
PL
1:
S2000-IP-03 Detector;
2:
Light Emitter;
3:
Alignment Guide;
4:
Mark and Bar, OPEN HERE;
Base Plate;
5:
MK-2 Recessed Mounting Kit for suspended ceilings
6:
(ordered separately).
1.3
Standard Delivery
Single-piece delivery:
– S2000-IP-03 Detector
– Instruction Manual
– Base Plate
– Address Label
– Individual Packing
Group delivery:
– S2000-IP-03 Detector
– Instruction Manual
– Base Plate
– Address Label
– Group Packing
Addressable
Addressable
5
device
device
S2000-IP
Figure 1. Connection Diagram
Figure 3
- 1 pc.;
- 1 copy;
- 1 pc.;
- 1 pc.;
- 1 pc.
- 10 pcs.;
- 1 copy;
- 10 pcs.;
- 10 pcs.;
- 1 pc.