bolid S2000M 설치 매뉴얼 - 페이지 3

{카테고리_이름} bolid S2000M에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. bolid S2000M 10 페이지. Fire and intrusion monitoring and control panel

4
CONNECTING PANEL
The S2000M's connectivity is described in Table 1.
connections shall be not less than 0.2 mm
Legend
Descriptions
0V
- power 10.2 ... 28.4 V (primary supply)
+U1
+ power 10.2 ... 28.4 V (primary supply)
0V
- power 10.2 ... 28.4 V (backup supply)
+U2
+ power 10.2 ... 28.4 V (backup supply)
A
RS-485 input/output
B
RS-485 inverse input/output
TxD
RS-232 data output
RxD
RS-232 input:
Printer ready signal (when connecting a printer) or data received (for other
operating modes of the RS-232 interface)
GND
RS-232 common circuit
Primary power supply
Backup power supply
RS-485
RS-232
Figure 3.
External Connections
4.1 Connecting RS-485 Lines
4.1.1 When installing RS485 line, it is recommended using twisted pair cable. If RS485 line
is 100 meters or longer, only a twisted pair must be used.
4.1.2 The Bus topology is recommended for the RS485 line (see Figure 4). If needed, the
RS485 trunk can be branched with short branches (no longer than 100 meters). Longer
branches shall be made using S2000-PI interface converter (see Fig. 6)
4.1.3 The maximum length of RS485 line is 3,000 meters, if cable of 0.5 mm
used. If cable of 0.2mm
longer than 1,200 meters. The RS485 line can be extended using the S2000-PI interface
converter as shown in Figure 5.
4.1.4 To connect the panel to RS485 interface, please connect A and B lines of RS485
interface to A and B terminals on terminal strip
http://bolid.ru/
2
in cross section and no more than 1.5 mm
0 V
+U1
0 V
+U2
A
B
TxD
RxD
GND
2
conductors is used, the recommended RS485 line length is no
The conductors of the cable for
Table 1: S2000M Connectivity
XT1
0V
+U1
0V
+U2
TxD
RxD
GND
2
.
A
B
2
conductors is
3