dormakaba 9000 Delayed Egress Exit Device Installation
Instructions
1.6
Key switch operation for device
Delayed Egress Mode:
audible alarm is off) . Initiated after power up, (DIP switch #2 in OFF position) authorized egress mode
or re-arm mode.
Nuisance Alarm Mode:
audible alarm sounds a short tone)
depressing touch bar.
Delay Mode:
Unit is armed and touch bar will not activate the latch bolt. (LED is solid yellow, audible alarm
sounds intermittent tone) . Unit remains in the delay mode for 15 seconds ( including nuisance time).
Initiated by holding the touch bar depressed past the nuidance alarm time (30 second delay mode option
available.) Once started, the delay mode is irreversible and automatically initiates the alarm mode.
Alarm Mode:
Unit is disarmed and touch bar will activate the latch bolt (LED is solid red, audible alarm
sounds continous tone)
the alarm mode until manually reset with key.
By-Pass Mode:
From the delayed egress mode; unit is continuously disarmed and touch bar will activate
the latch bolt (LED slowly flashes green, audible alarm is off). Initiated by rotating the key clockwise
(approximately 180 degrees), until switch engages, hold key until mode is activated.
disabled.
Re-arm Mode:
From alarm mode; unit goes to the delayed egress mode. Initiated by rotating the key
clockwise (approximately 180 degrees) until switch engages, hold key until mode is activated. From the
bypass mode; unit goes to the delayed egress mode. Initiated by rotating the key clockwise (approximately
180 degrees.) until switch engages, hold key until mode is activated.
Authorized Egress Mode:
will activate the latch bolt (LED quickly flashes green, audible alarm is off)
time unit returns to the delayed egress mode automatically. The authorized egress mode is initiated by
rotating the key counter-clockwise (approximately 180 degrees) until switch engages, hold key until
mode is activated. DPS input will not initiate during the initial egress time, but will terminate the egress time if
the DPS closes before the end of egress time. DPS input will initiate an alarm after the egress time if the DPS
is opened.
NOTE: The By-pass mode and Re-arm mode (orange wire) may be intiated externally from the terminal
connector. (Normally open dry contact to ground.) The Authorized Egress mode
initiated externally from the terminal connector (Normally open dry contact to ground). See page 6 for
addtional details.
Exit Device
6
Unit is armed and touch bar will not activate the latchbolt. (LED is solid green,
Unit is armed and touch bar will not activate the latch bolt. (LED is solid green,
DIP switch selectable for 0, 1, 2 or 3 seconds. (See page 2) Initiated by
. Initiated automatically from the delay mode and is irreversible. Unit remains in
Bypass/Re-arm
Rotate Clock-wise
Unit is disarmed for 5, 10, 15 or 20 seconds (DIP switch selectible) and touch bar
Rotate Counter Clock-wise
Authorized Egress
95011817 (1135-88) IDE-20
Key switch operation for device
DPS input is
The LED will return to solid green
. After the authorized egress
(white wire) may be
.
01-2020