Configuration
5. Configuration
Before starting
►
NOTICE
Before switching on, make sure that the device has been kept at the specified
ambient temperature (-20... +55 ° C) for at least 30 minutes.
Parameters of the module can be read, edited and saved with 'M110 Configurator' soft-
ware. The full list of parameters is shown in the Table 5.1.
Module has to be configured first before operating in RS485 network.
The following steps are required:
–
Install M110 Configurator on the PC.
–
The module should be connected to USB port of the PC over a USB/RS485 adapter
(not included). Connect the D+/D- terminals of the module with the D+/D- contacts of
the adapter.
–
Connect the power supply to 24V/0V terminals of the module.
–
Turn on the power supply.
–
Run the Mх110 Configurator.
If the factory settings of the module have not been changed, the connection to the mod-
ule is automatically established, the module automatically recognized, its configuration
parameters read out and an appropriate configuration mask open.
If it does not happen, parameters of the configurator have to be changed.
Table 5.1 Configuration parameters
Name
dev
bPS
LEn
PrtY
Sbit
A.Len
Addr
t.out
Prot
Rs.dL
Tin.C
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
Parameter
Device
ver
Firmware version
Baud rate, kbit/s
Data bits *
Parity *
Stop bits *
Address bits
Device address
Time-out, s
Protocol
Response delay, ms
Debouncing filter
Valid value
Common parameters
Up to 8 symbols
Up to 8 symbols
Network parameters
0
1
2
3
4
5
6
7
8
0
1
0
1
2
0
1
0
1
1...247
0...600
0
1
Modbus RTU
2
Modbus ASCII
0...45
Output parameters
0
1
Default set-
Meaning
tings
MV110-16D
manufactur-
er
2.4
4.8
9.6
14.4
19.2
9.6
28.8
38.4
57.6
115.2
7
8
8
none
even
none
odd
1
1
2
8
8
11
16
0
akYtec
0
2
off
0
on
9