Appendix B Connection to the Computer
Address
RW
hex
dec
Measured temperature, °C×100
0x0102 (4)0258
R
Measured humidity, %RH×100
0x0103 (4)0259
R
Calculated dew point, °C×100
0x0104 (4)0260
R
0% value for analog
0x0105 (4)0261 RW
output 1
100% value for analog
0x0106 (4)0262 RW
output 1
0% value for analog
0x0107 (4)0263 RW
output 2
100% value for analog
0x0108 (4)0264 RW
output 2
* The new value is applied after restart.
** Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the
device shall be the only Modbus instrument in the network. The device will not respond to Master command when
addressed by ID 0.
*** This value is dynamic and not kept in EEPROM after restart.
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 ·
Description
bit[5]=0/1 - in case of sensor absent, turn
on signaling with low current/high current
Bit [7] = 0/1 – current/voltage output de-
Supported values (dec)
on analog output2;
if bit[4]==0 this bit will be ignored
bit [6] = 0/1 – current/voltage output
detected on output1, read-only
tected on output2, read-only
signed integer, -4000...+12500
(-40.00...+125.00 °C)
signed integer, 0...+10000
(0.00...100.00 %RH)
signed integer, -8000...+10000
(-80.00...+100.00 °C)
signed integer, -1000...+1000
(-1000...+1000 °C/%RH)
signed integer, -1000...+1000
(-1000...+1000 °C/%RH)
signed integer, -1000...+1000
(-1000...+1000 °C/%RH)
signed integer, -1000...+1000
(-1000...+1000 °C/%RH)
Default
-
-
-
0
95
-20
(65516)
70