: PARAMETER SETTINGS OF GROUP 2
No
Menu
Number of Steps
4 0068
Step ON Delay Time (※1)
4 0074
Minimum Step ON Time (※2)
4 0075
Minimum Step OFF Time (※3)
4 0076
Delay Time between Steps (※4)
4 0067
Rotation (※5)
4 0069
Control Type
4 0070
Refrigerant selection
4 0061
(Saturated Temperature) (※6)
Pressure Sensor Offset (※7)
4 0072
Communication ID
4 0063
Communication BPS
4 0064
(※1) ON Delay Time: Although it is ON condition, it is turned on after ON Delay Time.
(※2) Minimum ON Time: Once the output is on, it is not turned off during the minimum ON time even if it is under the OFF condition.
(※3) Minimum OFF Time: Once the output is off, it is not turned on during the minimum OFF time even if it is under the ON condition.
(※4) Delay Time between Steps: Under the condition that multiple steps are turned on simultaneously, the lead step is turned on first and then the next step is on after Delay Time between Steps.
(※5) Rotation: It controls all the units evenly according to the predetermined ON/OFF and step parameters.
※ ON Rotation: ON - It turns on from the step which is being off the longest. OFF - The step which was on by step ON pressure turns off if it reaches its step OFF pressure.
※ ON/ OFF Rotation: ON - It turns on from the step which was off the longest. OFF - It turns off from the step which is being ON the longest.
(※6) Refrigerant selection: Display saturation temperature in accordance with selected refrigerant.
(※7) Offset: Offset the differential for pressure sensor.
e.g) If displayed pressure value: 0.20MPa and actual pressure value: 0.22MPa. It is offset by inputting +0.02MPa.
5.
COMMUNICATIONS SPECIFICATIONS
: Communication Model ( -R4 )
Description
Transmission line connection
Multiple line
Communications method
RS485 (2-wire, half-duplex)
BPS
BPS default 9600 BPS
Parity, Data, Stop bit
None, 8 Data, 1 Stop
Protocol Type
Modbus RTU MODE
Function Code
Read HOLD REGISTERS (0x03) , Preset Single Register (0x06)
Maximum Read Word
16 Word
Media Type
BELDEN 9841 / 9842, LG LIREV-AMESB
Poll interval
100msec
: HOLD REGISTERS
Address
Menu
4 0011
Output status code
Bit0
n1 Output status
Bit1
n2 Output status
Bit2
n3 Output status
4 0013
Alarm status code
Bit0
Pressure sensor faulty
4 0024
Display of pressure value
Display of saturation temperature
4 0027
for low pressure
(PRG Button Press for 5 seconds)
Code
Unit
SNO
-
DT
sec
sec
NT
sec
FT
sec
ST
ROT
OFF(0)= No Use, ON(1) = ON Rotation when On, ONF(2)= ON/OFF Rotation
CTR
DN
(0)= Depressurization Control
R22 (0)= R22
RFY
R23 (1)= R23
123 (2)= R-123
OFS
MPa
ID
-
48 (0)= 4800
96 (1)= 9600
BDR
Unit
Type
Size (Word)
-
Digital
INT 16
Digital
-
Digital
-
Digital
Digital
-
INT 16
Digital
-
Analog
MPa
INT 16
Analog
℃
INT 16
-4-
Step
Min
0
1
0
1
0
1
0
1
0
1
UP
(1)= Pressurization Control
124 (3)= R-124
407 (6)= R-407c
134 (4)= R-134a
410 (7)= R-410a
404 (5)= R-404a
507 (8)= R-507
-1.99
0.01
1
1
192 (2)= 19200
※ Pressure Unit Conversion Table
MPa
1MPa
1
1bar
1ⅹ10
1kgf/cm
9.80665ⅹ10
1psi
6.895ⅹ10
DPX200
Refer to bit status below
Bit
0 : OFF
Bit
0 : OFF
Bit
0 : OFF
Refer to bit status below
Bit
0 : Normal
-0.10 ~ 1.50
-150.0 ~ 200.0
Max
Default
3
3
999
0
999
0
999
0
999
5
ONF (2)
DN (0)
R22 (0)
1.99
0.00
255
1
384 (3)= 38400
96 (1)
bar
kgf/cm
1ⅹ10
1.0197162ⅹ10
1.450382ⅹ10
1
1.019716
1.4503824ⅹ10
9.80665ⅹ10
1
1.4223393ⅹ10
6.8947ⅹ10
7.0307ⅹ10
MMI
1 : ON
1 : ON
1 : ON
1 : Alarm
-10 ~ 150
-1500 ~ 2000
DPX100 R20141014
Custom
Setup
psi
1
Scale
-
-
-
-
-
-
1/100
1/10