Parameter Significance
Alarm signals
Attribute 83 provides the alarm signals. An alarm is set as soon as the encoder is recognizing a status that
may lead to a wrong encoder position. Upon recognising the alarm status, the relevant bit is set to logically
high.
The alarm is automatically reset after 2.5 s. The alarm flagbit (attribute 85) is also set with every alarm.
Warning signals
The encoder will transmit warning signals upon the internal encoder parameters being beyond the
tolerances. Contrary to alarm signals warning signals do not indicate a wrong position. Warnings are being
reset as soon as the parameter that was beyond the tolerances turns into a correct value again. The Warn-
Flagbit (attribute 88) is also set with every warning.
Offset
Attribute 91 comprises the parameter offset value. The offset value is calculated within the preset function
and will shift the position value by the calculated value. The preset function is applied after the scaling
function.
The offset value is not stored into the non-volatile memory until the service "save" is carried out.
Encoder type
Encoder type = 01: absolute encoder singleturn
Encoder type = 02: absolute encoder multiturn
General services
The Encoder Position Object supports the following services:
Code
0Eh
Get_Attribute_Single
10h
Set_Attribute_Single
05h
15h
16h
Manual_GXP8W_EN.doc
04.05.11
Service
Provides the contents of a selected attribute
Changes the value of a selected attribute.
The new value is not yet (!) stored into the non-volatile memory
Reset
Reset of all parameters to default
Restore
Restores all parameters of the non-volatile memory
Save
Saves all parameters in the non-volatile memory to be restored
again after mains off/on.
Significance