5.1) PHYSICAL LOCATION:
Charging areas should be clean and dry. The temperature of the charging
room should be between 32°F (0°C) and 77°F (25°C), with occasional and brief
periods of ambient temperature as high as 104°F (40°C). Combustible
materials, open flames and smoking should not be permitted near or in the
charging area.
*********************************
A BATTERY ON CHARGE WILL EMIT EXPLOSIVE GAS.
TO PREVENT GAS ACCUMULATION.
****************************************************************************
5.2) MOUNTING:
The LEGACY AND LEGACY GOLD charger cabinets must be mounted on a surface
constructed from non-combustible material, such as stone, brick, concrete or
metal. Mounting holes are provided in the frame for securing the charger.
Most chargers can be stacked up to three high. Contact the nearest
authorized representative for specific instructions, if stacking is
necessary.
5.3) INPUT POWER CONNECTION:
THE LEGACY and LEGACY GOLD chargers are shipped from the factory connected
for the input voltage specified on your purchase order.
located inside the door, indicates the factory set input voltage.
If the charger is to be used at a different AC voltage than is presently
set for, the charger may be adjusted to operate for the different AC
service. Refer to SECTION 8.2.1 CHANGING THE AC INPUT LINE VOLTAGE.
*********************************
VERIFY THE AC ELECTRICAL SERVICE IS DISCONNECTED AT THE SOURCE BEFORE
ATTEMPTING TO CONNECT AC POWER TO THE CHARGER.
****************************************************************************
The AC input terminals are identified by a red on white AC INPUT sticker
located on the base near the fuse block.
connected to the proper AC INPUT terminals within the charger cabinet.
The fuse block's input terminals are rated for 14 awg to 2 awg wire. The
recommended torque is listed on the fuse block itself. The ground lug is
rated for 14 awg to 6 awg wire with a recommended torque of 12 in lbs.
A bare wire, green or green with yellow stripe grounding wire is to be
connected from the Grounding Terminal within the charger cabinet to the
system ground. The Grounding Terminal is identified by a green on white
Ground Terminal Label on the charger base. If a system ground is not
available, the charger frame must be connected to a driven ground rod in
accordance with National and Local electrical codes. Proper application and
tight terminal connections are important in avoiding future problems.
6
SECTION 5
INSTALLATION
WARNING
********************************
VENTILATE THE CHARGING AREA
WARNING
********************************
The AC input cable is to be
A "STOP" label,