PF Power factor P / S, PF ≠ cos φ
APF Average power factor
F
Line frequency [Hz]
t
Temperature [°C]
thi Maximum measured temperature value [°C]
OPh Operating hours count [h]
tan Measured value of tangent φ
Bank parameters display
From the main menu press the key ▼ until
INFO appears on the right side of the display.
Then press the key ► to enter. Select the bank
with ▲ and ▼ and then press the key ► to
enter the selected bank menu.
CC Actual power [kvar]
Percentage of nominal value [%]
OC Number of operations
type of bank (auto, Foff, Fon, AL, Flty)
Manual Operation
From the main menu press the ▼ button until
MANUAL appears on the right side of the
display. Then press the ► button for 3 seconds
to enter.
Warning: in manual operation the automatic
control is not active!
In manual mode, the regulator freezes the
outputs to the current value. By pressing the
keys ▲ and ▼, a bank can be selected. The
status of the outputs is changed by pressing
the ► ( ) button. Output status is displayed. In
manual mode, the reconnect delay is not
working, but the capacitor discharge time block
is working. Leaving manual mode, the
regulator will continue to control without
disconnecting all the banks first.
Regulator safeties, in manual mode, are
disabled. It is recommended to always
return the controller to automatic mode
at
the
end
maintenance.

Automatic Operation

Press the key ◄ until you exit all the previous
menu.
The AUTO writing on the right side of the
display indicates that the controller algorithm is
running. When AUTO is not displayed, the
controller algorithm is not running. The reasons
for this last circumstance are: manual mode is
MU 03.21 IT EN rev.1 ed. 5/2017
of
programming
Cod. 381025
active,
controller
temperature is too high, the voltage is out of
the permitted values or the harmonic level is
too high.
Alarms
The regulator has an extensive diagnostic
system.
All
described in the menu structure. When an
alarm is on, the ALARM indication on the
display is flashing. An error code is displayed
on the display. Possible error codes are:
/
/

Technical data

Power and
Measurement
Voltage:
Current
Measurement:
is
deactivated,
possible
configurations
Voltage measurement out of
tolerance limits
Current measurement less than
15mA (check the amperometric
circuit)
The current measurement is too
high.
The target can not be reached
THDu alarm (too high harmonic
level)
One or more banks are
defective. The defective bank is
flashing along with the ALARM
indication.
One or more banks have a
power less than 50% of the
initial one. The bank number
and the error code flash
alternately.
Over temperature alarm. The
banks will be switched off one
by one.
The maximum number of hours
of operation has been reached.
Perform extraordinary
maintenance.
The maximum number of
switching cycles has been
reached on one or more banks.
Automatic initialization has been
interrupted due to poor load
conditions
90 – 550V AC, single phase, 45-
65Hz, 5VA, max. fuse 10A
PT ratio 1,0 .. 350,0
15mA – 6A, single phase, power
dissipation 20 mOhm,
CT ratio 1 .. 9600
the
are