2 Configuration

The Mxp-024 and Mxp-025 are pre-configured to show zone numbers 1...20.
The Mxp-013 can be configured from a DIL switch to any of the zone ranges in the table below.
Notes:
1. Mxp-013-050 indicates the first 50 zones in each of the ranges.

3 Operation:

When a zone changes state to a fire condition, the corresponding zone LED will illuminate. The Zone LED
Indicators will be turned off when the panel is manually reset.
The Mxp-013 incorporates a power saving feature so that in the event of a major fire with more than 50 zones
all in a fire condition occurring in the same zone range, the zone LED's will change from being continuously on
to flashing in order to minimise power drawn from the standby battery.

3.1 Testing the Zonal LED Indicators

Enter the "TEST" menu and select "DISPLAY". All of the zonal LED's will then flash on and off for several
seconds.