On the "Panel" Page:
Dev Info: This shows the device information, including device temperature, firmware version and the
serial number. If using a second annunciator panel, click on the "Panel 2" tab and verify the information
is populated.

Alarm Setting

The alarm indications on the annunciator panel(s) will always be synchronized with the Battery Backup
Unit. Users cannot change the first 7 dry contact alarms.
There are two other alarms "Comm Fault" and "Over TEMP". They can be enabled or disabled and can be
configured to trigger "Dry Contact Alarm 8" from annunciator panel(s)
Note: Many jurisdictions require that you monitor the integrity of the circuit for the dry contact alarms.
"Comm. Fault ALM" will fulfill this requirement.
Firmware: Upgrade the firmware, if necessary. If using two annunciator panels, be sure to update both
of them.
To upgrade firmware: Click on "Add File", select the new firmware file from your file explorer, then click
on "Upgrade". The device should upgrade then reboot.