Specifications
Electrical
§ Each ice machine and dispenser requires a separate circuit with electrical disconnect within 10 ft (6 m).
§ Equipment ground required.
§ Standard electrical – 230 V, 50 Hz, 1 phase
§ Connect to a dedicated circuit.
§ Maximum ice machine amperage – 5.5A.
§ Cord provided on ice machine.
Plumbing
§ 3/8" FPT water inlet
§ 3/4" MPT drain
Notes:
§ Slope to drain of 1/4" per foot (20 mm per 1 m run) with a 1/2" min. is recommended.
§ Water shut-off recommended within 10 feet (3 m), drain to be hard piped and insulated.
§ Separate drains for ice machine and condenser. To prevent back flow, do NOT connect drains.
§ Follett recommends a Follett water filter system be installed in the ice machine inlet water line (standard capacity
#00130229, high capacity #00978957, carbonless high capacity #01050442).
Ambient
Air temperature*
†
Water temperature
Water pressure
Condenser water
temperature
Condenser water
pressure
*
Ambient air temperature is measured at the air-cooled condenser coil inlet.
†
Ambient water temperature is measured in the ice machine reservoir.
Shipping weight
§ 73 kg (160 lb)
100 F/38 C max.
90 F/32 C max.
70 PSIG max. (482 kPA)
90 F/32.2 C max.
125 PSIG (862 kPA) max. 10 PSIG (68 kPA) min.
50 F/10 C min. (best performance below 80 F/27 C)
45 F/10 C min. (best performance below 70 F/21 C)
10 PSIG min. (68 kPA)
45 F/7.2 C min
MC_414A, MF_414A, R290 230 V/50 Hz Ice Machines