Dovre 2300GL 설치 지침 매뉴얼 - 페이지 6
{카테고리_이름} Dovre 2300GL에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Dovre 2300GL 18 페이지.
Convection air may be led to arrive from both
the room and outside (other room, cellar, exte-
rior) to the bottom side of the fireplace. In case
convection air is supplied (directly or indirectly)
from outside, it may also be useful as a supply
of fresh air for combustion.
At any rate, assure proper home air manage-
ment and sufficient air supply into the room.
Ensure not to use other air-consuming appli-
ances, such as heaters, cooking hoods, bath-
room ventilators, in the same room or in the
house while the stove is burning; or make sure
to have an extra ventilation grille installed for
these appliances.
3.1.3. Floor, walls
Combustible material must be sufficiently pro-
tected. The floor under the fireplace and the
walls around it must not contain elec tric wires.
Under the appliance
Under the appliance, any combustible material must be removed or specially
shielded by means of a 6 cm concrete slab and 10 cm insulation. The legs of the
appliance may rest directly on the concrete slab and insulation must be applied in-
between the legs.
Floor round the appliance
A floor made of combustible material must be properly shielded in the following
areas:
Front: height of the lower part of the fire chamber + 30 cm, but 60 cm at least.
Sides: height of the lower part of the fire chamber + 20 cm, but 40 cm at least.
Walls, ceiling
Combustible walls behind, next to, or above the fireplace must be shielded with at
least a 10 cm stone or brick wall and 10 cm insulation. Fireproof materials should be
covered with at least 6 cm insulation.
2300 - 2400
V > H + 30 > 60
S > H + 20 > 40
6
03.27997.000