Follett HMD1400R 설치 지침 매뉴얼 - 페이지 4

{카테고리_이름} Follett HMD1400R에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Follett HMD1400R 8 페이지.

Follett HMD1400R 설치 지침 매뉴얼
2.1
2.2
Condenser installation specifi cations
S-trap
required
P-trap
required
MODEL
CORPORATION
SERIAL NO
Easton Pennsylvania
PART NO
FULL LOAD AMPS
VOLTS
HZ
PHASE
SINGLE
MOTOR COMPRESSOR THERMALLY PROTECTED
REFRIGERANT
CHARGE
OZ
208264
DESIGN PRESSURE HIGH SIDE
LOW SIDE
PSIG
Module No.
Stock Module Identification Plate
MIN. BRANCH CIRCUIT AMPACITY
AMPS
UL
R
R
UL
NSF
MADE IN
THE USA
Product
MAX. BRANCH CIRCUIT FUSE SIZE
AMPS
C
Service No.
EVAPORATOR
UNIT
Site layout:
• Outdoor ambient temperature range: –20 F to 120 F (–29 C to 49 C)
• Installation with condenser unit elevations above 20' (6,1m) require an S-trap at the midpoint
of the rise
• Maximum line rise must not exceed 35' (10,7m)
• Maximum line set length must not exceed 100' (30,5m)
• Maximum line drop must not exceed 15' (4,6m)
Note: The service loop is not included when calculating the length, rise or drop
of the tubing run.
Note: 1400/1650 units only:
HCD1400/1650 condensing units contain a liquid to suction line heat exchanger. To maintain
optimum liquid refrigerant sub-cooling from the heat exchanger, the entire liquid line should
be insulated separately from the suction line.
4
100' max.
(30,5m)
EVAPORATOR UNIT LEVEL
100' max.
(30,5m)
CONDENSER UNIT
maximum
line rise
CONDENSER UNIT
CONDENSER UNIT
maximum
line drop
REMOTE CONDENSING UNIT
+35'
(+10,7m)
+20'
(+6,1m)
+3'
(+0,9m)
–15'
(–4,6m)