4 – Horizon Elite drain - specifier guidelines
Flush drain plumbing – For regular machine drainage
➊
Minimum 8"
radius
2 ft x 1" OD
silicone tubing
3/4" barb x 3/4" FPT
➋
3/4" MPT x 1" slip
➌
1" Stand pipe/drain
Chassis drain plumbing – To assist with condensate in high humidity areas
5 – Horizon Elite ice tube runs - specifier guidelines
Long tube runs for RIDE remote ice delivery equipment
beverage
dispenser
minimum of
6.00" (15.24 cm)
turn/corner
ice transport tube –
1 3/16" OD,
2 1/8" OD with insulation
Remote 1810, 2110 series ice machine
support
maximum
straps
2' (60.9 cm)
radius
transport tube slope
(toward ice machine)
1/4"
1'
(2 cm per meter)
Important specifier notes: Where code
allows, follow recommendation below.
1. Connect the silicone tubing to the ice machine
3/4" drain barb
2. Assemble the 3/4" barb x 3/4" FPT to the 3/4"
MPT x 1" slip. Connect the other end of the
silicone tubing to the 3/4" barb
3. Connect the 1" slip fitting to the 1" stand pipe/
➌
drain
.
Note: Minimum 8" radius on silicone drain line.
Drain line from the ice machine must have at least
1/4" per foot pitch (6.4 mm/0.3 m).
Note: Stand pipe/drain provided by others. All
other components provided with ice machine.
Important specifier notes: Where code
allows, follow recommendation below.
1. Plug must be removed from John Guest fitting.
2. Route 3/8" drain tubing through knockout in back
of docking station and insert fully into John Guest
fitting connection at the rear of the machine
chassis. Route other end of 3/8" drain tubing to
drain.
3. Drain must slope 1/4" inch per foot
(6 mm per 30.4 cm).
Important specifier notes
1. 75' (22.9 m) maximum ice transport
tube run.
2. Tubing routing bends must have a
6.00" (15.24 cm) radius or larger.
3. Dips and traps are not allowed. If not
supported from underneath, secure
insulated ice transport tube at least
every 2' (60.9 cm) to prevent drips
and traps.
4. Relative humidity levels above 80%
in areas where the ice machine or ice
transport tube is located may produce
excessive condensation that will cause
wall-mounted
water damage.
ice machine
5. Contact factory for recommendations
on running tubing through a decorative
soffit or chase.
➊
.
➋
.
7
Form# 8180