App Overview
Output The output page allows for monitoring the current state of the outputs of Amplink
device. The colored bars match the wire color of the corresponding output on Amplink
PDM. The output status is indicated by either a green dot for ON, red dot for FAULT, or
gray dot for OFF. By tapping an output, the Output Configuration page will appear.
Triggers Input triggers are configured from the triggers page. At least one trigger must be
active and set to "Voltage (+12V)" or "Ground (GND)." If using multiple triggers, select the
input signal it will respond to, choose either "Voltage (+12V)" or "Ground (GND)". Any
unused triggers should be set to disabled. The triggers have three states "Activated"
meaning the trigger has detected either Voltage or Ground, "Armed" meaning the trigger is
waiting for the desired voltage, or "Disabled" meaning the trigger will never be activated.
Output Configuration The configuration page is used to configure output settings
including: output name, amperage limit, time on, time off, trigger logic (and/or). Tap "Save"
to save the configuration to the Amplink. Tapping the back button will discard changes and
exit the configuration screen.
Name - tap the field to open the keyboard.
Amp limit - tap the field and enter the current limit.
AND Triggers – tap and select the triggers
OR Triggers – tap and select the triggers
Time On and Time Off – enter the time before the output turns on or off
Test – tap to turn Output on or off, exiting the screen will turn off the output.
Trigger logic examples:
To setup all outputs to respond to an ignition trigger, select T1 in the "OR Triggers"
and leave "And Triggers" set to None.
Other Examples:
AND Trigger set to T1,T2 – the output will turn on when both Trigger 1 and Trigger 2
are activated.
OR Trigger set to T1,T2 – the output will turn on when either Trigger 1 or Trigger 2 is
activated.