needs to use a hinged clamp core, (i.e. a split shield), while the power in cable can use either
type.
In the case of the power in (P1) EMI cable shield, the cable must turn through the core twice.
Each extra turn through the core markedly increases the impedance associated with the core
and provides more protection.
Position the EMI cable shield as close to the entry point of the cabinet as possible.
RS485 Communications
Cardax FT Controllers communicate with other Cardax FT units via high quality twisted pair
communications cable with low capacitance - typically Category 5 (CAT5) cable.
The twisted pair cable is polarised and needs to be terminated at the last, physical unit.
RS232 cabling
Communication via modem requires the RS232 cabling to be terminated in a DE9 socket and
connected to plug P3.
Balanced Inputs
Cabling should be a minimum size of 0.2 mm
To ensure correct tamper detection (short or open circuit), the balanced inputs require 4k7
ohm resistors to be connected as close as possible to the device being monitored.
When the monitored device incorporates a normally-closed tamper switch, it can be wired in
series with resistor R1.
Refer to Chapter 2 of the Cardax FT Installation manual for further information on connecting
inputs and resistors.
Output relays
The Cardax FT Controller 3000 has eight relay outputs, (i.e. two per group), PE1 to PE4 and
PF1 to PF4. Refer to the Component Layout within this Installation Note for wiring this plug.
The cabling to and from this relay plug must be capable of carrying sufficient current for the
device the relay is controlling. The relay contact can carry 5 Amps at 24 V DC/AC resistive
load.
Note: The connectors on the Cardax FT Controller 3000 accommodate both horizontal and
Part number 3E1089 R3
March 2003
5 V
Input
4k7
plug
GND
vertical wiring entry.
2
(24 AWG) for all inputs.
R1 4k7
R2
4k7
Alarm
sensor
3