5
Installation
5.1
Mounting the indoor unit
5.1.1
Guidelines when installing the indoor unit
INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment.
Depending on the field conditions, it might be easier to
install the optional equipment first.
▪ In case of installation with duct, but no duct service opening.
Modify the position of the air filters.
3
1
2
4
1 Remove the air filter(s) from the outside of the unit.
2 Remove the interchangeable plate.
3 Install the air filter(s) on the inside of the unit.
4 Reinstall the interchangeable plate.
▪ When installing an air inlet duct, select fixing screws that stick out
5 mm on the inside of the flange to protect the air filter from
damage during maintenance of the filter.
a
b
c
5 mm
a
Air inlet duct
b
Inside of the flange
c
Fixing screw
▪ Ceiling strength. Check whether the ceiling is strong enough to
support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.
▪ Installation options:
A
125
c
e
a
460
b
B
125
c
a
460
b
Class
35+50
60+71
FBA35~140A2VEB9+FBA35~71A2VEB9+ADEA35~125A2VEB
Split system air conditioners
4P456962-1D – 2018.08
d
f
d
f
f (mm)
760
1060
Class
100~140
A
Mounting the air inlet with a canvas connection
B
Mounting the air inlet panel directly
a
Ceiling surface
b
Ceiling opening
c
Air inlet panel (optional accessory)
d
Indoor unit (back side)
e
Canvas connection for air inlet panel (optional accessory)
NOTICE
The unit can be used with bottom suction by replacing the
interchangeable plate by the air filter holding plate.
a
Air filter holding plate with air filter(s)
b
Interchangeable plate
▪ Suspension bolts. Use M10 suspension bolts for installation.
Attach the hanger bracket to the suspension bolt. Fix it securely
using a nut and washer from the upper and lower sides of the
hanger bracket.
▪ Ceiling opening size. Make sure the ceiling opening is within the
following limits:
a
c d
b
630
800
Class
A (mm)
35+50
700
60+71
1000
100~140
1400
5 Installation
f (mm)
1460
a
b
a
d
4×
a1
b1
c1
b1
a2
B (mm)
738
1038
1438
Installation manual