Rotary switch
Example: "0"
Use an insulated screwdriver to set the dip switches.
Setting
Setting range
Indoor unit
0 to 63
address
Refrigerant
circuit
0 to 99
address
(1) Indoor unit address
Rotary switch (IU AD × 1) ....................Factory setting "0"
Rotary switch (IU AD × 10) ..................Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU
AD SW as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD × 1) .................Factory setting "0"
Rotary switch (REF AD × 10) ...............Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
Rotary Switch
Address
Setting
REF AD SW
Refrigerant circuit
× 10
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
.
.
.
.
.
.
99
9
Do no t set the indoor unit address (IU AD SW) at 64 to 99. It may result in failure.
En-13
Rotary switch
Example: "0"
CAUTION
Type of switch
Setting
example
2
IU AD x 10
Setting
example
63
REF AD x 10
Table A
Address
Rotary Switch Setting
IU AD SW
Indoor unit
× 1
× 10
0
0
0
1
1
0
2
2
0
3
3
0
4
4
0
5
5
0
6
6
0
7
7
0
8
8
0
9
9
0
0
10
1
1
11
1
2
12
1
.
.
.
.
.
.
.
.
.
9
63
6
(3) Remote controller address
Rotary switch (RC AD SW)....Factory setting "0"
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting
Remote controller
address
Example If 4 indoor units are connected.
Indoor unit
RC AD SW
IU AD x 1
Address
RC AD SW
Address
REF AD x 1
] 1

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up. (Fig. B)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Fig. B
Indoor unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP SW SET 3 SW1, SW2, referring to the Table B.
× 1
0
1
2
3
4
5
6
7
8
9
0
1
2
.
.
.
3
DIP SW
SET 3 SW1
DIP SW
SET 3 SW2
Setting range
Setting
0 to 15
example
Indoor unit
Indoor unit
RC AD SW
RC AD SW
RC AD SW
0
1
2
Remote
controller
0
1
2
3
0
1
2
3
8
9
A
B
8
9
10
11
Confusion
A
A
Dip switch
ON
"SET 3"
OFF
sw
sw
sw
sw
1
2
3
4
Table B
Custom code
A (Factory setting)
OFF
OFF
Type of switch
0
RC AD
Indoor unit
RC AD SW
3
4
5
6
7
4
5
6
7
C
D
E
F
12
13
14
15
Code change
B
C
D
B
C
D
B
C
D
ON
OFF
ON
OFF
ON
ON