L, N: Power supply cable
Cable clamp
Connect the
remote
controller cable
Set the DIP
DIP switch
switch (SW1)
(SW1)
*1: If you connect the remote controller cable to the terminal
Y3, 2-wire type remote controller does not work.
] 1
] 1
6.5. External input and external output (Optional
parts)
Controller PCB
Output terminal (CNB01)
(1) External input
• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
• "Operation/Stop" mode, "Emergency stop" mode or "Forced stop" mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
X1, X2:
Transmission
cable
Cable tie (Medium)
(Accessories)
Remote controller cable
Y1: Red
Y2: White
Y3: Black
For 2-wire type
For 3-wire type
Y1:Non-poler
Y1:Red
Y2:Non-poler
Y2:White
Y3:Do not connect *1
Y3:Black
2WIRE
3WIRE
(Factory setting)
Apply voltage terminal
(CNA03)
(CNA01)
Dry contact terminal
(CNA02)
(CNA04)
DIP switch
(SET 2)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
DC power supply
12 to 24V
Load
resistance
*a
Load
resistance
*a
Load
resistance
*a
connected unit
*1 Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
When connected to Apply voltage terminals of multiple indoor units with a connected unit, be sure
to make a branch outside the indoor unit using a pull box, etc. as shown on below example.
DC power supply
12 to 24V
Load
resistance
Load
resistance
connected unit
● Dry contact terminal ([CNA02], [CNA04])
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA02], [CNA04]).
*c
*c
Ch 1
Ch 2
*c
Ch 3
connected unit
*c Select very low current use contacts (usable at DC12V, DC1mA or less).
*d The wiring is different from Apply voltage terminals. Be suffi ciently careful when wiring.
When connected to Dry contact terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
K1
K2
K3
Input device 1
Input device 2
*1
P.C.B
CNA01
*b
CNA03
P.C.B
CNA01
P.C.B
CNA01
P.C.B
CNA01
P.C.B
CNA02
GND
*d
CNA04
P.C.B
K4
CNA02
P.C.B
K5
CNA02
P.C.B
K6
CNA02
K1 - K6: Relay
(Device for DC Current)
En-10