5.3.2 Transmission and Remote controller cable
Transmission cable
30 mm
Shield
cable
(no film)
40 mm
• Connect remote controller and transmission cables as shown in figure below.
GOOD
Different diameter
Tighten the terminal screws to the specified torques, otherwise, abnormal overheating
may be occurred and possibly cause serious damage inside the unit.
Tightening torque
M3 screw (Transmission /X1, X2)
(Remote controller /Y1, Y2)
To peel the sheath from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the wire by overtightening the
screw. On the other hand, an under tightened screw can cause faulty contact, which will
lead to a communication failure.
5.4. Wiring
5.4.1 Power supply cable
(1) Remove the terminal cover.
(2) Remove the cable clamp.
(3) Bend the end of the connection cable as shown in the figure.
(4) Connect the end of the connection cable fully into the terminal block.
(5) Fasten the connection cable with a cable clamp.
Power supply
cable
Terminal cover
Remote controller cable
30 mm
PROHIBITED
Connect to 1 side
WARNING
0.5 to 0.6 N•m (5 to 6 kgf•cm)
CAUTION
L
N
Earth
(ground)
Cable clamp
5.4.2 Transmission and remote controller cable
Push mount cable
tie (accessories)
Cut
X1, X2: Transmission cable
Y1, Y2: Remote controller cable
5.4.3 EV kit cable connecting (EEV external model only)
Earth (ground) wire of EV kit cable
EV kit cable
Connect
After connecting the EV kit cable, slide the tube (included with
the EV kit) over the connector to protect it.
Tube
Connect
Connect the earth (ground) wire of the EV kit cable
to the earth (ground) terminal of the terminal block.
Earth (Ground) wire
of the EV kit cable
Connection part of
the EV kit cable
Cable tie (Small)
Push mount
cable tie
(accessories)
En-8