AirStage ARXA36GALH 설치 매뉴얼 - 페이지 4
{카테고리_이름} AirStage ARXA36GALH에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. AirStage ARXA36GALH 18 페이지. Indoor unit (duct type)
3. INSTALLATION WORK
Correct initial installation location is important because it is diffi cult to move unit after it is
installed.
3.1. Selecting an installation location
Select installation locations that can properly support the weight of the indoor. Install
the units securely so that they do not topple or fall.
Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside.
It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
• Area fi lled with mineral oil or containing a large amount of splashed oil or steam, such
as a kitchen.
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as sulfuric
gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause
refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon fi bers or
fl ammable dust, or volatile infl ammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a fi re.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or fl ammable gas.
Install the unit where drainage does not cause any trouble.
Install the indoor unit, power supply cable, transmission cable, and remote controller
cable at least 1 m away from a television or radio receivers. The purpose of this is to
prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still receive noise under
some signal conditions.)
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
• Decide the mounting position with the customer as follows:
(1) Install the indoor unit on a place having a suffi cient strength so that it withstands
against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) A place from where the air can be distributed evenly throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit (or RB unit) is easy.
(6) Install the unit where the connection pipe can be easily installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibrations are not amplifi ed.
(9) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the fi lter can be removed.
(10) Providing as much space as possible between the indoor unit and the ceiling will
make work much easier.
(11) If installing in a place where its humidity exceeds 80%, use heat insulation to
prevent condensation.
3.2. Installation dimensions
• Provide the space around the unit as shown in the following fi gure.
400 mm or more
1
*
400 mm or more when drain from drain pipe.
• Provide a service hole for inspection purposes.
• Do not place any wiring or illumination in the service space, as they will impede service.
• When an air fi lter is installed on the air inlet, provide enough service space to replace
the fi lter.
En-3
WARNING
CAUTION
150 mm or more *1
300 mm
Service hole
or more
Control box
500 mm
or more
300 mm
or more
Control box
1,550 mm or more
3.3. Installing the unit
Install the air conditioner in a location which can withstand a load of at least 5 times the
weight of the main unit and which will not amplify sound or vibration. If the installation
location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
3.3.1. Installing the hangers
Hanging bolt installation diagram.
(Top side)
740 mm
477 mm
(Right side)
Air
Air
Air
Service space
Intake panel
Air
WARNING