AirStage ARXK14GCLH 설치 매뉴얼 - 페이지 17

{카테고리_이름} AirStage ARXK14GCLH에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. AirStage ARXK14GCLH 19 페이지. Indoor unit (duct type)

AirStage ARXK14GCLH 설치 매뉴얼

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor
unit
Remote
controller
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2 referring to the Table B.
ON
OFF
SW
SW
SW
1
2
3
Table B
A (Factory setting)
DIP switch SET3 SW1
DIP switch SET3 SW2

7.3. Static pressure mode

If the applicable static pressure does not match the static pressure mode, the static
pressure mode may be changed to another mode manually.
Recommended range of external static pressure
AR07/09/12: 0 Pa to 30 Pa
AR14/18/24: 0 Pa to 50 Pa
It is necessary to set up a static pressure mode for each usage of static pressure.
Static pressure can be set at site.
Relation between set values and static pressure are as the following table.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
Function Number
Setting Number
26
Setting static pressure becomes "30Pa" if AR07/09/12 is set to "04" through "05".
Code change
A
B
C
A
B
C
Dip switch "SET 3"
SW
4
Custom code
B
C
OFF
ON
OFF
OFF
OFF
ON
CAUTION
Setting Static Pressure
00
0 Pa
01
10 Pa
02
20 Pa
03
30 Pa
04
40 Pa
05
50 Pa
AR07/09/12 : 10 Pa
31
AR14/18/24 : 15 Pa
7.4. Switching of airfl ow direction louver function
When auto louver grille (Optional parts) is attached, set the airfl ow direction louver func-
tion "Valid".
The airfl ow direction louver of auto louver grille can be operated by the remote controller
while the airfl ow direction louver function is valid.
Installation method
D
Set the DIP switch SET 4 SW2, SW2 referring to the Table D.
D
Table D
DIP switch
SET 4 SW2
D
ON
ON
ON
DIP switch "SET 4"
OFF
SW SW SW SW
1
2
3
4
Airflow direction louver function "Invalid"
OFF
(Factory setting)
ON
Airflow direction louver function "Valid"
En-16