AirStage ASUA4TLAV1 설치 매뉴얼 - 페이지 7
{카테고리_이름} AirStage ASUA4TLAV1에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. AirStage ASUA4TLAV1 16 페이지.
4.3.3 Pipe connection
When the flare nut is tightened properly by your hand, hold the body side coupling with a
separate spanner, then tighten with a torque wrench.
Be sure to install the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the flare nut cannot tightened smoothly. If the flare
nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the indoor unit pipe until immediately before connect-
ing the connection pipe.
Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as
this would reduce the lifetime of the units.
Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to
tighten the flare nut correctly.
Flare nut
Tightening torque
[in (mm)]
[lbf·ft (N·m)]
1/4 (6.35) dia.
11.8 to 13.3 (16 to 18)
3/8 (9.52) dia.
23.6 to 31.0 (32 to 42)
1/2 (12.70) dia.
36.1 to 45.0 (49 to 61)
5/8 (15.88) dia.
46.5 to 55.3 (63 to 75)
3/4 (19.05) dia.
66.4 to 81.1 (90 to 110)
5. ELECTRICAL WIRING
Electrical work must be performed in accordance with this Manual by a person certified
under the national or regional regulations. Be sure to use a dedicated circuit for the unit.
An insufficient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fire.
Before starting work, check that power is not being supplied to the all units.
Use the included connection cables and power cables or ones specified by the
manufacturer. Improper connections, insufficient insulation, or exceeding the allowable
current can cause electric shock or fire.
For wiring, use the prescribed type of cables, connect them securely, making sure that
there are no external forces of the cables applied to the terminal connections. Improp-
erly connected or secured cables can cause serious accidents such as overheating the
terminals, electric shock, or fire.
Do not modify the power cables, use extension cables, or use any branches in the wir-
ing. Improper connections, insufficient insulation, or exceeding the allowable current can
cause electric shock or fire.
Match the terminal board numbers and connection cable colors with those of the out-
door unit (or RB unit). Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends of
the wiring, can cause a malfunction, electric shock, or fire.
Always fasten the outside covering of the connection cable with the cable clamp. (If the
insulator is chafed, electric discharge may occur.)
Securely install the electrical box cover on the unit. An improperly installed electrical box
cover can cause serious accidents such as electric shock or fire through exposure to
dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
We suggest installing GFEB breakers or follow local electrical code. When installing
this system, install using ground fault equipment breakers (GFEB) to reduce the risk of
leaking current which result in electric shock or potential fire.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Connect the connection cable firmly to the terminal board. Imperfect installation may
cause a fire.
If the supply cable is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
CAUTION
Tighten with 2 wrenches.
Flare
Torque
nut
wrench
Indoor unit pipe
Connection pipe
(Body side)
WARNING
Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
Do not connect power supply cable to the transmission or remote controller terminals,
as this will damage the product.
Never bundle the power supply cable and transmission cable, remote controller cable
together.
Separate these cable by 2 in (50 mm) or more.
Bundling these cables together will cause miss operation or breakdown.
When handling PCB, static electricity charged in the body may cause malfunction of the
PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor units for more than 10 seconds to discharge static
electricity charged in the body.
Holding
• Do not touch terminals of parts and patterns implemented on PCB.
wrench
5.1. Electrical requirement
• Select the power cable type and size
in accordance with relevant local and
national regulations.
• Specifications for local wiring power cord and branch wiring are in compliance with local
code.
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire
diameter when the wire length is long.
Breaker should be installed at every refrigerant system. Do not use a breaker in a different
refrigerant system.
Refer to the table for the breaker specifications of each installation condition. Perform
the power crossover wiring within the range of the same refrigerant system. When the
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B
below.
A. Current breaker requirements
Model
MCA
ASUA4TLAV1
0.22 A
ASUA7TLAV1
0.32 A
ASUA9TLAV1
0.52 A
ASUB30TLAV1
0.90 A
ASUB36TLAV1
1.18 A
If the capacity of connected RB units and indoor units exceeds the upper limit, either add
breakers or use a breaker with a greater capacity.
B. Earth leakage breaker requirements
Breaker capacity
30 mA, 0.1 sec or less
100 mA, 0.1 sec or less
5.1.1 Cable specifi cations
Transmission
22 AWG
cable
(0.33 mm²)
22 AWG to 16 AWG
Remote con-
(0.33 to 1.25 mm²)
troller cable
(2-wire type)
18AWG
CAUTION
Voltage rating
Operating range
• MCA: Minimum Circuit Ampacity
MAX. CKT. BKR
• MAX. CKT. BKR : Maximum Circuit
(Fuse capacity)
Breaker
When the power crossover wiring is
done, make it so that the total of the
15 A
MCA of the connected RB units and
indoor units does not exceed the 11 A.
For RB unit MCA, refer to the RB unit
installation manual.
*1: Heat pump type: indoor units,
Maximum connect-
Heat recovery type: indoor units
able "indoor units"
and RB units.
or "indoor units +
*2: If the 100 mA capacity breaker is
RB units" (*1)
not provided, split the quantity of
36 or less
the indoor units into small groups
of 9 units or less and provide a
37 to 121 (*2)
breaker with capacity of 30 mA for
each group.
Cable size
Cable type
LEVEL 4 (NEMA) non-polar
2 core, twisted pair solid core
diameter 0.026 in (0.65mm)
Sheathed PVC cable
Thermostat cable 2 core
208/230 V
187 to 253 V
Remarks
LONWORKS ®
compatible cable
Non polar 2 core,
twisted pair
Use sheathed non
twisted pair cable
En-6