AirStage ASUB24RLAV 설치 매뉴얼 - 페이지 10

{카테고리_이름} AirStage ASUB24RLAV에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. AirStage ASUB24RLAV 17 페이지. Indoor unit (wall mounted type)
AirStage ASUB24RLAV에 대해서도 마찬가지입니다: 운영 매뉴얼 (8 페이지)

AirStage ASUB24RLAV 설치 매뉴얼
*1 Make the power supply DC 12 to 24 V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24 V across pins 1-2, and 1-3.
*a The allowable current is DC 5~10 mA. (Recommended: DC 5 mA)
Provide a load resistance such that the current becomes DC 10 mA or less.
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3.
Connect correctly.
When connected to voltage terminals of multiple indoor units with a connected unit, be
sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
DC power
supply 12-24 V
Load
resistance
Load
resistance
Connected unit
• No voltage terminal ([CN17])
When a power supply is unnecessary at the input device you want to connect, use the no
voltage terminal ([CN17]).
*c
*c
Ch 2
Ch 1
Connected unit
*c Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*d The wiring is different from voltage terminals. Be suffi ciently careful when wiring.
When connected to no voltage terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
When connected to multiple indoor units directly, it will cause breakdown.
Input device 1
Input device 2
En-9
P.C.B
CN6
P.C.B
CN6
P.C.B
CN6
P.C.B
1
CN17
2
3
GND
*d
P.C.B
K1
K4
CN17
P.C.B
K2
K5
CN17
P.C.B
K3
K6
CN17
K1~K6: Relay
(Device for DC Current)
Operation behavior
• Input signal type
The input signal type can be selected.
It is switched by Dip-sw on the indoor
unit PCB.
Dip-sw [Set 2-2]
OFF
ON
• When function setting is "Start/Stop" mode
In the case of "Edge" input
Connector
Input signal
OFF → ON
Ch1 of CN6 or CN17
ON → OFF
In the case of "Pulse" input
Connector
Ch1
CN6 or CN17
Ch2
* The last command has priority.
* The indoor units within the same remote controller group operates in the same mode.
• When function setting is "Emergency stop" mode
In the case of "Edge" input
Connector
Ch1 of CN6 or CN17
In the case of "Pulse" input
Connector
Ch1
CN6 or CN17
Ch2
* All indoor units of same refrigerant system stops when Emergency stop operates.
• When function setting is "Forced stop" mode
In the case of "Edge" input
Connector
Ch1 of CN6 or CN17
In the case of "Pulse" input
Connector
Ch1
CN6 or CN17
Ch2
* When the forced stop is triggered, indoor unit stops and Start/Stop operation by a
remote controller is restricted.
When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
"Start/Stop" mode or "Emergency stop" mode, "Forced stop" mode can be selected with
function setting of indoor unit.
Edge
Input signal type
Pulse
Edge
The width of pulse
Pulse
must be longer than
200 msec.
Command
Operation
Stop
Input signal
Command
OFF → ON
OFF → ON
Input signal
Command
OFF → ON
Emergency stop
ON → OFF
Normal
Input signal
Command
OFF → ON
Emergency stop
OFF → ON
Input signal
Command
OFF → ON
Forced stop
ON → OFF
Normal
Input signal
Command
OFF → ON
Forced stop
OFF → ON
CAUTION
Operation
Stop
Normal
Normal