Drazice OKC 160 NTR / BP 운영 및 설치 매뉴얼 - 페이지 9

{카테고리_이름} Drazice OKC 160 NTR / BP에 대한 운영 및 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Drazice OKC 160 NTR / BP 13 페이지. Stationary water heaters
Drazice OKC 160 NTR / BP에 대해서도 마찬가지입니다: 작동 및 설치 매뉴얼 (17 페이지), 작동 및 설치 매뉴얼 (12 페이지), 작동 및 설치 매뉴얼 (20 페이지), 작동 및 설치 매뉴얼 (20 페이지), 작동 및 설치 매뉴얼 (18 페이지), 운영 및 설치 매뉴얼 (20 페이지), 작동 및 설치 매뉴얼 (18 페이지)

Drazice OKC 160 NTR / BP 운영 및 설치 매뉴얼
8.

PRESSURE LOSSES

9.

EXAMPLES OF HEATERS CONNECTION

Connecting a heater to a heating circuit
The heater is placed on the ground, next to the heating source, or in its vicinity. The heating circuit is connected to
marked inputs and outputs of the heater exchanger; the deaerating valve is mounted in the highest place. It is
necessary to install a filter into the circuit in order to protect the pumps, the three-way valve, and backflow flaps,
and the exchanger from sedimentation. It is recommended to flush the heating circuit before the assembly. All
wiring connections must be properly insulated from heat.
If the system works with priority heating of HSW using a three-way valve, always follow the installation
instructions of the three-way valve's manufacturer.
Connecting a Heater to a Hot Water Distribution
Cold water shall be connected to an inlet marked with a blue ring and writing "HSW INLET". Hot water shall be
connected to an outlet marked with a red ring or writing "HSW OUTLET". If the hot service water (HSW)
distribution is equipped with circulation circuit, it shall be connected to the outlet marked with "CIRCULATION".
For potential drain of heater, the HSW inlet has to be provided with a "T" fixture with a drain valve. Each
individually lockable heater must be at the cold water inlet provided with a stop gate, test cock, safety valve with a
reverse flap and a pressure gauge.
An example of a group heater connection for steady hot water consumption from all tanks using
Tichelmann's method
OV – Heating water
SV - Cold water
C - circulation
TUV - Hot service water
1 - Return valve
2 - pump
9