Wiring
Typical Wiring Diagrams for -T & -B Outputs
B-Type -
840 W maximum. 120 Vac heater. (Non-inductive loads only) For larger loads, replace heater connections
with contactor, as required. Maximum inductive load rating is 3 A at 120 V and 1.5 A at 240 V. The N.C.
contacts can be used for cooling.
terminal 10 and fuse both of the supply legs.
T-Type -
CAUTION
solid state relay with SPST contacts. The -T units can handle contactors or resistive loads up to 1 A with 10 A
Possible fire hazard.
inrush maximum. For -T units use a 1 A, 250 V fast blow fuse.
Because these
controls or associated
equipment may not
always fail safe, an
approved temperature
and/or pressure
safety control should
be used for safe
operation.
For 240 Vac supply move the connection shown on terminal 9 to
Note:
Figure 2. Typical 120 Vac for -B & -T Output