AIR & REFRIGERANT CIRCUITS:
Air Circuit
Warm wet compressed air enters the refrigerant dryer at the inlet port. (On models 30
scfm through 250 scfm) It first passes through an air-to-air heat exchanger where its
temperature is lowered by the cool air exiting the dryer. It then enters the evaporator or
refrigerant-to-air heat exchanger where its temperature is lowered. The condensate
(water) generated by the cooling action is collected in the moisture separator and
automatically removed. The dry air then leaves the separator, and enters the air to air
heat exchanger (30 scfm through 250 scfm models only) where it is heated and the air
exits through outlet port.
Refrigerant Circuit
The refrigerant compressor compresses refrigerant vapor to a high pressure and
temperature. The compressed vapor then flows through the condenser where it is
cooled and forms a liquid. After this, it is filtered through the refrigerant filter-dryer
where any traces of moisture and contaminants are removed. The expansion valve
lowers the pressure which in turn lowers the temperature of the liquid refrigerant to its
preset level. It remains at this pressure and vaporizes as it flows through the
evaporator/refrigerant-to-air heat exchanger absorbing heat from the air being dried.
The refrigerant then flows back to the compressor and the cycle repeats.
The dryer uses R134a refrigerant. For units with a refrigerant suction pressure gauge,
the refrigerant suction pressure is listed in chart below for the appropriate model. If a
lower pressure dew point is required, back off the adjustment screw on the expansion
valve until gauge pressure reaches the desired level.
Model Number
SD10 through SD20
SD30 through SD40
SD50 through SD100
SD150 through SD250
Gauge Pressure Reading
33 to 38 psig
29 to 33 psig
30 to 34 psig
31 to 35 psig
5