CARNES HXHAS 소유자 매뉴얼 - 페이지 8

{카테고리_이름} CARNES HXHAS에 대한 소유자 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. CARNES HXHAS 20 페이지. Commercial humidistat

installation
outdoor air temperature Sensor installation
When outdoor air temperature is very low, condensation can occur on
windows and other surfaces which may cause damage to the structure. To
minimize this risk, the outdoor air temperature sensor should be installed.
The outdoor air temperature lowers the humidity setpoint to a safe level,
where the indoor relative humidity is too low to condense. The outdoor
temperature compensation control adjusts the maximum humidity setpoint
according to the values shown in Table 1. The humidistat will automatically
detect if the outdoor air temperature sensor is connected and control the
relative humidity setpoint accordingly.
table 1: Maximum setpoint based on outdoor air temperature
outdoor air
temperature (°F)
-30
-20
-10
0
10
20
30
40
45
>45
8
|
CommerCial humidiStat
outdoor air
temperature (°C)
-34.4
-28.9
-23.3
-17.8
-12.2
-6.7
-1.1
4.4
7.2
>7.2
adjusted maximum
humidity Setpoint
(rh%)
10
15
20
25
30
35
40
45
47.5
Unadjusted
Form 16767