a. Common configuration (calibration)
Note
In the lower part, you can read in real time (periodic sampling of 2s) the value measured by the
module.
✓ Analog measurement
Here you can choose the type of measured value (current or voltage). You must also make
this choice on the slide switch (see Set Up).
✓ Calibration
The 'Unit' field allows you to specify the unit of measure for data readability, up to 4
characters long. The 'minimum value' allows to set the minimum value for a sensor output
of 0V or 4mA. The 'maximum value' is used to set the maximum value for a sensor output
of 10V or 20mA.
✓ Offset
Offset correction of the sensor + module assembly. Enter the value to add or subtract to the
measure to get the correct value. It is not recommended to correct the offset for an input of
0V or 0mA.
ATIM_ACW-DINDA_UG_FR_v1.5