Drehmo i-matic 설치 및 운영 매뉴얼 - 페이지 16

{카테고리_이름} Drehmo i-matic에 대한 설치 및 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Drehmo i-matic 18 페이지. Electrical actuator with integral controls
Drehmo i-matic에 대해서도 마찬가지입니다: 사용 설명서 (20 페이지)

Supplement operating manual for DREHMO i-Matic actuators with integrated
2.5.2 Actuator i-Matic for Ex-Zone acc. ATEX device category 2 G – DiM-X1X
2.5.2.1

Connection with copper cable

The connection of the modbus signal lines (A, B) from inputs and outputs have to be done on the appropriate
terminals in the termination compartment. If the actuator is not the last node on the bus, the necessary T-
piece may be made up by means of using the available double terminals (A1, B1, A2, B2) which are
electrically connected. A bridge between incoming and outgoing bus signals has to be made to achieve the
required T-piece.
The bus terminator always has to be provided near or downstream of the last bus device for correct bus
termination. If the last bus device is an i-Matic type DREHMO actuator, the terminator can be activated by
connecting terminals Tx+ with Bx and Tx- with Ax (see next picture), (x = number of channel).
Connection of two Profibus systems to an i-Matic drive
-
-
-
Devices for use in explosive areas have a spur length of approximately 40 cm for each channel.
Wenden, 21.03.12
Prepared by: Ste
MODBUS fieldbus interface
channel 1: leading to the next device
channel 2: last device on the segment (terminator activated)
Page 16 of 18